Charging VAR of 132 kV equilateral line
Short answer
With symmetrical spacing 6 m and r=1.1 cm, per-phase capacitance = 8.828 nF/km. Three-phase charging VAR = V_L² ω C_n = 48.3 kVAR/km (16.1 kVAR/km per phase).
A 50 Hz, 132 kV, 3-phase overhead transmission line has symmetrical phase spacing of 6 m. The effective radius of the phase conductor is 1.1 cm. Compute the charging VAR per unit length generated by the line.
With symmetrical spacing, per phase, and the three-phase charging VAR is .
Data: m, cm m, 132 kV, 50 Hz.
Capacitance per phase
Capacitive reactance
Charging current and VAR
Per phase: kVAR/km.
Answer: charging VAR kVAR per km for the three-phase line (16.1 kVAR/km per phase).
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Charging current of 60 Hz horizontal 132 kV line · Power System Analysis I, chapter 4
- Charging current of 132 kV line, 6 m equilateral · Power System Analysis I, chapter 4
- 400 kV twin-bundle line: reactances and charging VAR · Power System Analysis I, chapter 4 · asked 2×
- 400 kV line with 3-conductor bundles: reactances and VAR · Power System Analysis I, chapter 4 · asked 3×
- 132 kV horizontal line: susceptance and charging · Power System Analysis I, chapter 4
- ACSR 132 kV line: parameters and charging MVA · Power System Analysis I, chapter 4
- Minimum conductor spacing for 230 kV corona limit · High Voltage Engineering, chapter 5 · asked 4×
- Conductor selection, 100 MW 70 km 132 kV · Transmission and Distribution System Design, chapter 4
- Air clearances for 132 kV double circuit line · Transmission and Distribution System Design, chapter 4
- Audible noise of 750 kV line (20 kV/cm gradient) · High Voltage Engineering, chapter 5 · asked 3×