- Asked 2/20
- 2070 Bhadra · 8 marks
Arrester current and resistance (Z = 300 Ω)
Short answer
Line current before arrester is 10 kA. Arrester current is 14.33 kA, arrester resistance 118.6 Ω. Voltage reflection coefficient is -0.433 and refraction coefficient 0.567.
For a 750 kV line, take Vw = 3000 kV crest, travelling on the line and Vp = 1700 kV. The line surge impedance is Z = 300 ohms. Calculate (a) the current flowing in the line before reaching the arrestor, (b) the current through the arrestor, and (c) the value of arrestor resistance for this condition and also find the reflection and refraction coefficient of voltage.
When the surge reaches the arrester, the arrester conducts and holds the voltage at its protective level . It acts as a shunt resistance at the end of the line, and the travelling-wave relations give the currents.
Data
- Incident surge, kV (crest)
- Protective level, kV
- Line surge impedance,
(a) Current in the line before reaching the arrester
(b) Current through the arrester
Reflected voltage: kV. Reflected current: kA.
(c) Arrester resistance
Reflection and refraction coefficients of voltage
Check: , and kV .
| Quantity | Value |
|---|---|
| Line current before arrester | 10 kA |
| Reflected voltage | −1300 kV |
| Arrester current | 14.33 kA |
| Arrester resistance | 118.6 Ω |
| Voltage reflection coefficient | −0.433 |
| Voltage refraction coefficient | 0.567 |
The arrester current (14.33 kA) is larger than the line current (10 kA) because the negative reflected voltage wave carries a positive current. The arrester must be rated for this current.
Answer: (a) 10 kA, (b) 14.33 kA, (c) ; , .
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Arrester current and resistance for 750 kV line · High Voltage Engineering, chapter 4 · asked 2×
- Arrester current, resistance and rating on 132 kV line · High Voltage Engineering, chapter 4
- Arrester with 1000 kV BIL on 300 Ω line · High Voltage Engineering, chapter 4 · asked 3×
- Arrester with 1600 kV BIL on 300 Ω line · High Voltage Engineering, chapter 4 · asked 3×
- Transformer BIL and arrester resistance for 500 kV line · High Voltage Engineering, chapter 4
- Arrester with 1000 kV BIL on 350 Ω line · High Voltage Engineering, chapter 4 · asked 3×