Coordination with residual voltage 200 Id^0.25 (PR 1.25)

Short answer

Residual voltage Vres = 200 × 24^0.25 = 442.67 kV. Protective ratio PR = 500/442.67 = 1.13, below required 1.25. Coordination is insufficient; the arrester can only maintain the margin up to 16 kA discharge current.

A transformer is protected by a lightning arrester at the incoming line. The BIL withstand voltage of the transformer is chosen to be 500 kV. The protective ratio required for transformer protection is 1.25. A lightning strike at the arrester causes an arrester discharge current of 24 kA. Check whether the transformer is properly coordinated? Assume arrester residual voltage can be approximated by: 200 Id^0.25.

The transformer is properly coordinated only if the arrester residual voltage at the given discharge current is low enough that BILVres≥\dfrac{\text{BIL}}{V_{res}} \ge the required protective ratio (1.25).

Data

  • BIL of transformer = 500 kV
  • Required protective ratio, PR=1.25PR = 1.25
  • Arrester discharge current, Id=24I_d = 24 kA
  • Residual voltage characteristic: Vres=200 Id0.25V_{res} = 200\, I_d^{0.25} kV (IdI_d in kA)

Step 1: Residual voltage of the arrester

Vres=200×(24)0.25=200×2.2134=442.67 kV\begin{aligned} V_{res} &= 200 \times (24)^{0.25} \\ &= 200 \times 2.2134 \\ &= 442.67\ \text{kV} \end{aligned}

Step 2: Protective ratio actually obtained

PRactual=BILVres=500442.67=1.13PR_{actual} = \frac{\text{BIL}}{V_{res}} = \frac{500}{442.67} = 1.13

Step 3: Compare with the requirement

The maximum residual voltage allowed for PR=1.25PR = 1.25 is

Vres,max=BILPR=5001.25=400 kVV_{res,max} = \frac{\text{BIL}}{PR} = \frac{500}{1.25} = 400\ \text{kV}
QuantityValue
Residual voltage at 24 kA442.67 kV
Maximum allowed residual voltage400 kV
Protective ratio obtained1.13
Protective ratio required1.25

Since 442.67 kV>400 kV442.67\ \text{kV} > 400\ \text{kV} (or 1.13<1.251.13 < 1.25), the protective margin is not enough.

Step 4: Largest discharge current the arrester can handle with PR = 1.25

200 Id0.25=400Id=(400200)4=16 kA\begin{aligned} 200\, I_d^{0.25} &= 400 \\ I_d &= \left(\frac{400}{200}\right)^4 = 16\ \text{kA} \end{aligned}

So the arrester keeps the required margin only for discharge currents up to 16 kA; a 24 kA discharge exceeds this.

Remedies

  • Use an arrester with a lower protective level (lower rating or better non-linear blocks, e.g. ZnO).
  • Choose a transformer with a higher BIL: at least 1.25×442.67=553.31.25 \times 442.67 = 553.3 kV, i.e. the next standard level above it, 650 kV.
  • Reduce the stroke current reaching the arrester by better shielding of the line near the substation.

Answer: Vres=442.67V_{res} = 442.67 kV, giving PR=1.13<1.25PR = 1.13 < 1.25, so the transformer is NOT properly coordinated (the required margin holds only up to Id=16I_d = 16 kA).