Coordination with residual voltage 200 Id^0.25 (PR 1.25)
Short answer
Residual voltage Vres = 200 × 24^0.25 = 442.67 kV. Protective ratio PR = 500/442.67 = 1.13, below required 1.25. Coordination is insufficient; the arrester can only maintain the margin up to 16 kA discharge current.
A transformer is protected by a lightning arrester at the incoming line. The BIL withstand voltage of the transformer is chosen to be 500 kV. The protective ratio required for transformer protection is 1.25. A lightning strike at the arrester causes an arrester discharge current of 24 kA. Check whether the transformer is properly coordinated? Assume arrester residual voltage can be approximated by: 200 Id^0.25.
The transformer is properly coordinated only if the arrester residual voltage at the given discharge current is low enough that the required protective ratio (1.25).
Data
- BIL of transformer = 500 kV
- Required protective ratio,
- Arrester discharge current, kA
- Residual voltage characteristic: kV ( in kA)
Step 1: Residual voltage of the arrester
Step 2: Protective ratio actually obtained
Step 3: Compare with the requirement
The maximum residual voltage allowed for is
| Quantity | Value |
|---|---|
| Residual voltage at 24 kA | 442.67 kV |
| Maximum allowed residual voltage | 400 kV |
| Protective ratio obtained | 1.13 |
| Protective ratio required | 1.25 |
Since (or ), the protective margin is not enough.
Step 4: Largest discharge current the arrester can handle with PR = 1.25
So the arrester keeps the required margin only for discharge currents up to 16 kA; a 24 kA discharge exceeds this.
Remedies
- Use an arrester with a lower protective level (lower rating or better non-linear blocks, e.g. ZnO).
- Choose a transformer with a higher BIL: at least kV, i.e. the next standard level above it, 650 kV.
- Reduce the stroke current reaching the arrester by better shielding of the line near the substation.
Answer: kV, giving , so the transformer is NOT properly coordinated (the required margin holds only up to kA).
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Coordination with residual voltage 200 Id^0.25 (PR 1.2) · High Voltage Engineering, chapter 4 · asked 2×
- Arrester coordination for 8000 kV strike · High Voltage Engineering, chapter 4 · asked 2×
- Transformer BIL and arrester resistance for 500 kV line · High Voltage Engineering, chapter 4
- Arrester coordination for 40 kA discharge · High Voltage Engineering, chapter 4 · asked 2×
- Transformer BIL and maximum arrester distance · High Voltage Engineering, chapter 4
- Arrester separation for a 500 kV/μs surge · High Voltage Engineering, chapter 4
- Arrester 100 m from transformer coordination · High Voltage Engineering, chapter 4