- 2070 Magh · 6 marks
220 kV line on 6-6-12 m triangle
Short answer
Inductance 1.257 mH/km, capacitance 9.219 nF/km, capacitive reactance 1726.4 Ω, charging current 73.6 A, total charging MVAR 28.0 MVAR.
A 220 kV, 50 Hz, 200 km long 3-phase line has its conductors on the corners of a triangle with sides 6 m, 6 m, and 12 m. The conductor radius is 1.81 cm. Find the inductance and capacitance per phase per km, capacitive reactance per phase, charging current and total charging MVAR.
Sides of 6, 6 and 12 m mean the conductors are actually in a straight line (flat configuration with 6 m between adjacent conductors). For a transposed line use .
Data: cm m, m, 220 kV, 50 Hz, 200 km.
Inductance per phase per km
Capacitance per phase per km
Capacitive reactance per phase (200 km)
Charging current
Total charging MVAR
Answer: mH/km, nF/km, , A, MVAR.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Inductance and capacitance of 4-conductor bundle line · Power System Analysis I, chapter 4
- Capacitive reactance and charging of 2-conductor bundle line · Power System Analysis I, chapter 4 · asked 2×
- 400 km long line, 60 MVA at 220 kV · Power System Analysis I, chapter 5
- 400 kV line with 3-conductor bundles: reactances and VAR · Power System Analysis I, chapter 4 · asked 3×
- 12 km line at 32.5 kV: regulation and capacitor · Power System Analysis I, chapter 6
- Capacitor for zero regulation, 70 km 220 kV line · Power System Analysis I, chapter 6
- Conductor selection, 220 kV line for 200 MW · Transmission and Distribution System Design, chapter 4
- Capacitance and charge matrices (9.81 m clearance) · High Voltage Engineering, chapter 5 · asked 3×
- Air clearances, 220 kV line for 200 MW · Transmission and Distribution System Design, chapter 4
- Conductor selection, 100 MW 70 km 132 kV · Transmission and Distribution System Design, chapter 4