150 km line, A = 0.96∠1°: regulation, max power

Short answer

Sending end voltage = 132.87 kV, regulation = 25.82%; the line supplies about 2.28 MVAr (sending end provides 20.22 MVAr of the 22.5 MVAr load demand); maximum transferable power ≈124.0 MW.

A 3-phase long line of about 150 km has the following parameters: A = D = 0.96∠1.0° and B = 100∠80°. For a load of 30 MW at 0.8 p.f. lag, 110 kV, find (i) sending end voltage and regulation of the line (ii) reactive power supplied by the line (iii) maximum power that can be transferred on the line if sending and receiving end voltages are the same as in the question.

Data: A=D=0.96∠1∘A = D = 0.96\angle1^\circ, B=100∠80∘ ΩB = 100\angle80^\circ\ \Omega, load 30 MW at 0.8 pf lag, VRV_R = 110 kV. CC from AD−BC=1AD - BC = 1: C=(A2−1)/B=8.53×10−4∠77.84∘C = (A^2-1)/B = 8.53\times10^{-4}\angle77.84^\circ S.

(i) Sending-end voltage and regulation

VR=110/3=63.51∠0∘ kVIR=30×1063×110×103×0.8=196.82∠−36.87∘ AAVR=60.97∠1∘ kVBIR=19.68∠43.13∘ kVVS=AVR+BIR=76.71∠10.91∘ kV\begin{aligned} V_R &= 110/\sqrt3 = 63.51\angle0^\circ\ \text{kV} \\ I_R &= \frac{30\times10^6}{\sqrt3\times110\times10^3\times0.8} = 196.82\angle-36.87^\circ\ \text{A} \\ AV_R &= 60.97\angle1^\circ\ \text{kV} \\ BI_R &= 19.68\angle43.13^\circ\ \text{kV} \\ V_S &= AV_R + BI_R = 76.71\angle10.91^\circ\ \text{kV} \end{aligned}

Line value =3×76.71=132.87= \sqrt3\times76.71 = 132.87 kV.

%VR=∣VS∣/∣A∣−∣VR∣∣VR∣×100=76.71/0.96−63.5163.51×100=25.82%\%VR = \frac{|V_S|/|A| - |V_R|}{|V_R|}\times100 = \frac{76.71/0.96 - 63.51}{63.51}\times100 = 25.82\%

(ii) Reactive power supplied by the line

IS=CVR+DIR=174.38∠−19.35∘ ASS=3VSIS∗=34.66+j20.22 MVA\begin{aligned} I_S &= CV_R + DI_R = 174.38\angle-19.35^\circ\ \text{A} \\ S_S &= 3V_SI_S^* = 34.66 + j20.22\ \text{MVA} \end{aligned}

Load reactive power QR=30×0.75=22.5Q_R = 30\times0.75 = 22.5 MVAr.

QS−QR=20.22−22.5=−2.28 MVArQ_S - Q_R = 20.22 - 22.5 = -2.28\ \text{MVAr}

The sending end supplies only 20.22 MVAr, so the line itself supplies about 2.28 MVAr net to the load (its charging MVAr exceeds its I2XI^2X consumption).

(iii) Maximum power transfer

With ∣VS∣|V_S| = 132.87 kV and ∣VR∣|V_R| = 110 kV, maximum PRP_R occurs at δ=β\delta = \beta:

PR,max=∣VS∣∣VR∣∣B∣−∣A∣∣VR∣2∣B∣cos⁡(β−α)=132.87×110100−0.96×1102100cos⁡79∘=146.15−22.16=123.99 MW\begin{aligned} P_{R,max} &= \frac{|V_S||V_R|}{|B|} - \frac{|A||V_R|^2}{|B|}\cos(\beta-\alpha) \\ &= \frac{132.87\times110}{100} - \frac{0.96\times110^2}{100}\cos79^\circ \\ &= 146.15 - 22.16 = 123.99\ \text{MW} \end{aligned}

Answer: (i) VSV_S = 132.87 kV, regulation 25.82 %; (ii) the line supplies ≈ 2.28 MVAr (the sending end gives 20.22 MVAr of the 22.5 MVAr load); (iii) PmaxP_{max} ≈ 124.0 MW.

✓ Answer checked by Claude Opus 5.5 (high effort)