- 2075 Bhadra · 8 marks
150 km line, A = 0.96∠1°: regulation, max power
Short answer
Sending end voltage = 132.87 kV, regulation = 25.82%; the line supplies about 2.28 MVAr (sending end provides 20.22 MVAr of the 22.5 MVAr load demand); maximum transferable power ≈124.0 MW.
A 3-phase long line of about 150 km has the following parameters: A = D = 0.96∠1.0° and B = 100∠80°. For a load of 30 MW at 0.8 p.f. lag, 110 kV, find (i) sending end voltage and regulation of the line (ii) reactive power supplied by the line (iii) maximum power that can be transferred on the line if sending and receiving end voltages are the same as in the question.
Data: , , load 30 MW at 0.8 pf lag, = 110 kV. from : S.
(i) Sending-end voltage and regulation
Line value kV.
(ii) Reactive power supplied by the line
Load reactive power MVAr.
The sending end supplies only 20.22 MVAr, so the line itself supplies about 2.28 MVAr net to the load (its charging MVAr exceeds its consumption).
(iii) Maximum power transfer
With = 132.87 kV and = 110 kV, maximum occurs at :
Answer: (i) = 132.87 kV, regulation 25.82 %; (ii) the line supplies ≈ 2.28 MVAr (the sending end gives 20.22 MVAr of the 22.5 MVAr load); (iii) ≈ 124.0 MW.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- 110 km, 110 kV line: sending end, regulation, efficiency · Power System Analysis I, chapter 6 · asked 2×
- Regulation and efficiency of 100 km, 110 kV line · Power System Analysis I, chapter 6 · asked 2×
- Nominal-T 100 km line, 20 MW at 110 kV · Power System Analysis I, chapter 5
- 220 kV line, 200 MW: sending end from ABCD · Power System Analysis I, chapter 6
- 150 km line by T-model, 60 MW · Power System Analysis I, chapter 5
- 70 km, 40 MW line: regulation and zero-regulation pf · Power System Analysis I, chapter 6
- Conductor selection, 100 MW 70 km 132 kV · Transmission and Distribution System Design, chapter 4
- Empirical formula; voltage for 150 MW over 100 km · Transmission and Distribution System Design, chapter 2
- Conductor selection, 100 MW 80 km, no corona · Transmission and Distribution System Design, chapter 4
- Conductor selection, 220 kV line for 200 MW · Transmission and Distribution System Design, chapter 4