Economical span, double circuit, five spans
Short answer
The most economical span is 275 m, yielding the minimum tower weight per km of 30.06 t/km. It is determined by computing base bending moment and tower weight via Ryle's formula for each span and selecting the least weight per km.
To transmit a given amount of power to a given distance a double circuit line with a double earth wire is chosen for which the following design steps are completed, compute the most economical span.
| Span | Dmax (m) | h1 (m) | h2 (m) | h3 (m) | Ht (m) |
|---|---|---|---|---|---|
| 250 m | 5.27 | 12.178 | 14.998 | 17.818 | 28.444 |
| 275 m | 6.24 | 13.148 | 15.968 | 18.788 | 29.414 |
| 300 m | 7.30 | 14.208 | 17.028 | 19.848 | 30.474 |
| 325 m | 8.43 | 15.338 | 18.158 | 20.978 | 31.604 |
| 350 m | 9.65 | 16.558 | 19.378 | 22.198 | 32.824 |
Where h1: height of lower conductor from ground, h2: height of middle conductor from ground, h3: height of top conductor from ground, Ht: total height of tower. The power conductor has maximum working tension of 6000 kg and diameter of 4 cm. The earth wire has maximum working tension of 2000 kg and diameter of 2 cm. Assume maximum conductor deviation of 5° is permissible for all towers and the wind force is 100 kg/m².
The most economical span gives the minimum tower weight (cost) per km of line. For each span, compute the base bending moment of a 5° deviation tower, then the tower weight from Ryle's formula, then the weight per km.
Tower weight is taken from Ryle's formula (as given with IOE papers):
Here is in ft, is the bending moment at the base in klb-ft, and FS = 2 (assumed). The conversions are 1 m = 3.281 ft and 1 kg·m = 0.007233 klb-ft. Tower cost is taken as proportional to tower weight, and the number of towers per km is about . So the span with the least tower weight per km is the most economical.
Loads and bending moment
For each span the loads on a tower are found as follows. The wind span is taken equal to the span.
- Each power conductor (6 of them, 2 at each height ):
- Each earth wire (2 of them, at height ):
- Bending moment at the base:
Wind on the tower body is neglected because it is about the same for all spans.
All towers are designed for the maximum permissible deviation θ = 5°, so .
Sample calculation for L = 250 m, θ = 5°:
Results for all spans
| Span L (m) | (kg) | (kg) | M (kg·m) | (t) | Towers/km | Weight/km (t) |
|---|---|---|---|---|---|---|
| 250 | 1523.4 | 674.5 | 175,460 | 7.522 | 4.000 | 30.090 |
| 275 | 1623.4 | 724.5 | 198,157 | 8.267 | 3.636 | 30.061 |
| 300 | 1723.4 | 774.5 | 223,283 | 9.092 | 3.333 | 30.305 |
| 325 | 1823.4 | 824.5 | 250,773 | 9.992 | 3.077 | 30.745 |
| 350 | 1923.4 | 874.5 | 281,041 | 10.986 | 2.857 | 31.390 |
Steps followed:
- and increase with span because the wind span increases.
- increases because both the loads and the heights (, which include the sag) increase.
- increases, but the number of towers per km falls.
- The product, weight per km, is lowest at 275 m (30.061 t/km). It is only slightly higher at 250 m (30.090 t/km) and then rises clearly from 300 m onwards.
t/km
31.4 | *
30.7 | *
30.3 | *
30.1 | * *
+--+------+------+------+------+--
250 275 300 325 350 span (m)
Answer: the most economical span is 275 m, with a tower weight of 8.267 t per tower and 30.06 t per km.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Most economical span, double circuit line · Transmission and Distribution System Design, chapter 4 · asked 6×
- Economical span, double circuit, A/B/C towers · Transmission and Distribution System Design, chapter 4 · asked 5×
- Economical span, 200 km, A/B/C tower types · Transmission and Distribution System Design, chapter 4 · asked 6×
- Economical span, double circuit, 5° deviation · Transmission and Distribution System Design, chapter 4 · asked 4×
- Economical span, 200 km, 10% angle towers · Transmission and Distribution System Design, chapter 4 · asked 2×
- Most economical span, 180 km single circuit · Transmission and Distribution System Design, chapter 4
- T/F: double earth wire for 400 kV single circuit · Transmission and Distribution System Design, chapter 3
- T/F: earth wire choice depends on circuit and voltage · Transmission and Distribution System Design, chapter 3
- Most economical span from sag table · Transmission and Distribution System Design, chapter 4 · asked 2×
- Most economical EHV span from sag table · Transmission and Distribution System Design, chapter 4 · asked 2×
- Block diagram reduction: G1–G4 with H1, H2, H3 · Control Systems, chapter 3 · asked 3×
- Block diagram reduction: G1–G4 with H1, H2, H3 loops · Control Systems, chapter 3 · asked 2×
All Transmission and Distribution System Design chapter 4 questions →