L and C of triple-bundle line, D=8 m
Short answer
Using Deq = 10.08 m; bundle self-GMDs for inductance 0.1416 m and capacitance 0.1539 m. Inductance = 0.853 mH/km (170.6 mH for 200 km), capacitance = 13.30 nF/km (2.66 µF for 200 km).
Compute the inductance and capacitance per phase for a 200 km line using phase conductors of 18 mm radius and configured as given below. Assume complete transposition of the line. [Figure: horizontal single-circuit line; each phase is a triangular bundle of three sub-conductors with spacing d = 45 cm; centres of adjacent phases D = 8 m apart.]
Each phase is a 3-conductor bundle (equilateral triangle, side ). The bundle self-GMD is , with for inductance and for capacitance.
o o o
o o o o o o
a 8 m b 8 m c
d = 45 cm, r = 18 mm
Data: m, m, m, m, 200 km.
GMDs
Inductance per phase
Capacitance per phase
Answer: mH per phase (0.853 mH/km); F per phase (13.30 nF/km).
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Inductance of twin-bundle line, 16 mm radius · Power System Analysis I, chapter 4 · asked 3×
- Inductance and capacitance of 4-conductor bundle line · Power System Analysis I, chapter 4
- Capacitance of double circuit line, 6 mm radius · Power System Analysis I, chapter 4
- Inductance of 4-conductor bundle line, 6 m spacing · Power System Analysis I, chapter 4 · asked 2×
- Capacitance of double circuit line, 9 mm radius · Power System Analysis I, chapter 4
- Single-phase line capacitance, 6 mm, 1.3 m · Power System Analysis I, chapter 4
- Inductance of composite-conductor single-phase line · Power System Analysis I, chapter 4
- Insulator discs per string, 180 MW over 200 km · Transmission and Distribution System Design, chapter 3
- Initial line design for 200 MW over 120 km · Transmission and Distribution System Design, chapter 2
- Capacitance matrix of 400 kV bundled line · High Voltage Engineering, chapter 5 · asked 2×
- 6° phase shift per 100 km of lossless line · High Voltage Engineering, chapter 3