- 2067 Mangsir (old course) · 8 marks
RI of 330 kV line at point M
Short answer
RI per phase: 31.43 dB (far), 38.77 dB (centre), 39.29 dB (near) using CIGRE formula with distances 48.08, 37.70, 27.78 m and gradients 16.0, 17.1, 16.0 kV/cm. Line RI = (38.77+39.29)/2 + 1.5 = 40.5 dB above 1 μV/m.
With the help of transmission line and data given below, calculate the RI level of each phase at point M at 500 kHz in fair weather condition using CIGRE formula. Also calculate the RI level of the line. [Figure: three phase conductors in flat horizontal configuration spaced 11 m apart at a height of 14 m above ground; point M on the ground 46 m horizontally from the farthest outer conductor] Nominal voltage = 330 kV Bundle spacing = 45.72 cm Conductor diameter = 30 mm Number of conductors per phase = 2 Maximum surface gradient at central and outer phases at 330 kV are 1710 kV/m and 1600 kV/m respectively. The CIGRE formula is given by RIi(dB) = 3.5Em + 6d − 33 log10(Di/20) − 30, where Em in kV/cm, d in cm, Di in m.
RI from each phase is computed with the CIGRE formula using its distance to point M. The line RI is then obtained by the CIGRE rule for combining phase values.
Data
- Flat horizontal, m, m; M on the ground, 46 m horizontally from the farthest outer conductor
- , mm cm, cm
- centre = 1710 kV/m = 17.1 kV/cm; outer = 1600 kV/m = 16.0 kV/cm
- 500 kHz (0.5 MHz), fair weather:
far centre near
o--11 m---o--11 m---o H=14 m
/////////////////////////////////[M]
|<------------- 46 m ----------->|
Step 1: Horizontal and direct distances to M
Horizontal distances are 46 m (far outer), 35 m (centre) and 24 m (near outer).
Step 2: RI of each phase
; ; .
| Phase | (kV/cm) | (m) | RI (dB) |
|---|---|---|---|
| Near outer | 16.0 | 27.78 | 39.29 |
| Centre | 17.1 | 37.70 | 38.77 |
| Far outer | 16.0 | 48.08 | 31.43 |
Step 3: RI level of the line
CIGRE rule: if the highest phase value exceeds the others by 3 dB or more, the line RI equals it; otherwise take the average of the two highest plus 1.5 dB. Here 39.29 and 38.77 differ by only 0.52 dB, so
Answer: phase RI at M = 39.29 dB (near outer), 38.77 dB (centre), 31.43 dB (far outer); line RI ≈ 40.5 dB above 1 μV/m at 500 kHz in fair weather.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- RI of 400 kV line at 0.5 MHz · High Voltage Engineering, chapter 5
- RI levels of 400 kV line at 1 MHz · High Voltage Engineering, chapter 5
- Radio interference of 765 kV line by CIGRE · High Voltage Engineering, chapter 5
- Inductance matrix of 500 kV bundled line · High Voltage Engineering, chapter 5 · asked 3×
- Audible noise of 750 kV line (formula with Di) · High Voltage Engineering, chapter 5 · asked 3×
- Charge matrix of 400 kV line · High Voltage Engineering, chapter 5
- 330 kV quad-bundle line: inductance and charging · Power System Analysis I, chapter 4
- 132 kV horizontal line: susceptance and charging · Power System Analysis I, chapter 4
- Charging current of 60 Hz horizontal 132 kV line · Power System Analysis I, chapter 4
- Design: 330 m head plant, 132 kV · Power Plant Design, chapter 4 · asked 12×