- 2073 Bhadra · 8 marks
Balanced circulating current: 10 kV alternator
Short answer
Primary operating current = 1.8×200 = 360 A; Vph = 5774 V. Unprotected = (360×10)/5774 = 0.6235 (62.35%). To protect 80% of winding, maximum earthing resistance = 0.2×5774/360 = 3.21 Ω.
An alternator rated at 10 kV protected by the balanced circulating current system has its neutral grounded through a resistance of 10 ohms. The protective relay is set to operate when there is out of balance current of 1.8 A in the pilot wires, which are connected to the secondary windings of 1000/5 ratio current transformers. Determine: (i) the percentage winding which remain unprotected (ii) The minimum value of earthing resistance required to protect 80% of the winding.
For an earth fault at fraction x of the winding from the neutral, the fault current is x·V_ph / R_n (winding impedance neglected). The relay operates when the CT secondary out-of-balance current reaches 1.8 A.
Data: 10 kV, star; R_n = 10 Ω; setting 1.8 A; CT 1000/5 (ratio 200).
Step 1: Primary operating current
I_op = 1.8 × 200 = 360 A
V_ph = 10 000 / √3 = 5773.50 V
(i) Percentage unprotected
x × V_ph / R_n = I_op
x = 360 × 10 / 5773.50 = 0.6235
So 62.35% of the winding (from the neutral) is unprotected and only 37.65% is protected. The large earthing resistance limits the fault current too much.
(ii) Earthing resistance to protect 80%
Unprotected part allowed = 20% (x = 0.2):
0.2 × V_ph / R = 360
R = 0.2 × 5773.50 / 360 = 3.208 Ω
Answer: (i) 62.35% of the winding is unprotected; (ii) the earthing resistance must be reduced to 3.21 Ω (or less) to protect 80% of the winding.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Merz-Price: protected winding (13.8 kV) · Switchgear and Protection, chapter 7 · asked 2×
- Earth fault protection: 20 MVA alternator · Switchgear and Protection, chapter 7
- Pilot current with tap change (10 MVA) · Switchgear and Protection, chapter 7
- Circulating current vs balanced voltage differential · Switchgear and Protection, chapter 7
- Differential protection: 11 kV, 100 MVA generator · Switchgear and Protection, chapter 7
- Why and how the neutral is grounded · Switchgear and Protection, chapter 5 · asked 4×
- Neutral reactance/resistance to limit L-G current · Power System Analysis II, chapter 5
- Arrester current, resistance and rating on 132 kV line · High Voltage Engineering, chapter 4
- Line currents with isolated and grounded neutral · Power System Analysis II, chapter 4
- Arrester current and resistance for 750 kV line · High Voltage Engineering, chapter 4 · asked 2×