Fault current: four 1600 kVA generators
Short answer
Using 11 kV phase voltage 6350.85 V and generator reactance 15.125 Ω, four parallel generators plus 10 Ω feeder give 13.781 Ω, so fault current is 460.83 A, 115.21 A per generator. With 5 Ω bus reactors between A-B and C-D, total current is 443.57 A; G1/G4 supply 95.16 A each, G2/G3 supply 126.62 A each.
Below figure shows 4 Nos of identical generators operating in parallel. Each generator is rated as 1600 kVA, 11kV, Xg = 0.2 pu. [Figure: G1, G2, G3, G4, each through Xg, connected to an 11 kV busbar at points A, B, C, D; an outgoing feeder from the busbar between B and C through a circuit breaker and a reactor X = 10 Ω, with a 3-phase to ground fault at its end] (i) Calculate fault current in outgoing feeder and fault current supplied by each generator. (ii) If reactors of 5 ohm each are connected between point A and B, point C and D respectively. Calculate fault current in outgoing feeder and fault current supplied by each generator.
Work in ohms at 11 kV. Phase voltage V. Fault current .
G1 G2 G3 G4
|Xg |Xg |Xg |Xg
A--[5]--B----+---C--[5]--D 11 kV bus
| ([5] only in part ii)
CB
|
X=10 ohm
|
F
(i) Without bus reactors
All four generators are directly in parallel:
Each generator supplies A. (Fault MVA MVA.)
(ii) With 5 Ω reactors between A–B and C–D
G1 and G4 now reach the feeder through 5 Ω; G2 and G3 connect directly.
The bus voltage behind the reactors is V, so
Check: A.
Answer: (i) = 460.83 A, each generator 115.21 A. (ii) = 443.57 A; G1 and G4 supply 95.16 A each, G2 and G3 supply 126.62 A each.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Fault current: two 50 MW generators, reactor inductance · Power Plant Equipment, chapter 4
- Fault current: 50 MW and 40 MW generators · Power Plant Equipment, chapter 4
- Fault level: adding a third generator · Power Plant Equipment, chapter 4
- Bus-bar reactor scheme with four generators · Power Plant Equipment, chapter 4 · asked 2×
- Fault level: three generators, feeder reactor · Power Plant Equipment, chapter 4
- Fault current: two 500 kVA alternators · Power Plant Equipment, chapter 4
- Fault through impedance at bus 2 · Power System Analysis II, chapter 3
- Regulation of delta connected 1600 kVA alternator · Electric Machines II, chapter 1
- L-L fault current in kA at bus 3 · Power System Analysis II, chapter 5
- SLG fault at mid-line through 4.033 Ω · Power System Analysis II, chapter 5