Fault current: four 1600 kVA generators

Short answer

Using 11 kV phase voltage 6350.85 V and generator reactance 15.125 Ω, four parallel generators plus 10 Ω feeder give 13.781 Ω, so fault current is 460.83 A, 115.21 A per generator. With 5 Ω bus reactors between A-B and C-D, total current is 443.57 A; G1/G4 supply 95.16 A each, G2/G3 supply 126.62 A each.

Below figure shows 4 Nos of identical generators operating in parallel. Each generator is rated as 1600 kVA, 11kV, Xg = 0.2 pu. [Figure: G1, G2, G3, G4, each through Xg, connected to an 11 kV busbar at points A, B, C, D; an outgoing feeder from the busbar between B and C through a circuit breaker and a reactor X = 10 Ω, with a 3-phase to ground fault at its end] (i) Calculate fault current in outgoing feeder and fault current supplied by each generator. (ii) If reactors of 5 ohm each are connected between point A and B, point C and D respectively. Calculate fault current in outgoing feeder and fault current supplied by each generator.

Work in ohms at 11 kV. Phase voltage Vph=11000/3=6350.85V_{ph} = 11000/\sqrt3 = 6350.85 V. Fault current If=Vph/XtotalI_f = V_{ph}/X_{total}.

Zbase=1121.6=75.625 ΩXg=0.2×75.625=15.125 Ω\begin{aligned} Z_{base} &= \frac{11^2}{1.6} = 75.625\ \Omega \\ X_g &= 0.2\times75.625 = 15.125\ \Omega \end{aligned}
  G1      G2       G3      G4
  |Xg     |Xg      |Xg     |Xg
  A--[5]--B----+---C--[5]--D   11 kV bus
               |       ([5] only in part ii)
              CB
               |
            X=10 ohm
               |
               F

(i) Without bus reactors

All four generators are directly in parallel:

Xpar=15.1254=3.781 ΩXtotal=3.781+10=13.781 ΩIf=6350.8513.781=460.83 A\begin{aligned} X_{par} &= \frac{15.125}{4} = 3.781\ \Omega \\ X_{total} &= 3.781 + 10 = 13.781\ \Omega \\ I_f &= \frac{6350.85}{13.781} = 460.83\ \text{A} \end{aligned}

Each generator supplies 460.83/4=115.21460.83/4 = 115.21 A. (Fault MVA =3×11×0.46083=8.78=\sqrt3\times11\times0.46083 = 8.78 MVA.)

(ii) With 5 Ω reactors between A–B and C–D

G1 and G4 now reach the feeder through 5 Ω; G2 and G3 connect directly.

XG1=XG4=15.125+5=20.125 Ω1Xpar=220.125+215.125=0.23161Xpar=4.3176 ΩXtotal=4.3176+10=14.3176 ΩIf=6350.8514.3176=443.57 A\begin{aligned} X_{G1} = X_{G4} &= 15.125 + 5 = 20.125\ \Omega \\ \frac{1}{X_{par}} &= \frac{2}{20.125} + \frac{2}{15.125} = 0.23161 \\ X_{par} &= 4.3176\ \Omega \\ X_{total} &= 4.3176 + 10 = 14.3176\ \Omega \\ I_f &= \frac{6350.85}{14.3176} = 443.57\ \text{A} \end{aligned}

The bus voltage behind the reactors is IfXpar=443.57×4.3176=1915.2I_f X_{par} = 443.57\times4.3176 = 1915.2 V, so

IG1=IG4=1915.220.125=95.16 AIG2=IG3=1915.215.125=126.62 A\begin{aligned} I_{G1} = I_{G4} &= \frac{1915.2}{20.125} = 95.16\ \text{A} \\ I_{G2} = I_{G3} &= \frac{1915.2}{15.125} = 126.62\ \text{A} \end{aligned}

Check: 2(95.16)+2(126.62)=443.572(95.16) + 2(126.62) = 443.57 A.

Answer: (i) IfI_f = 460.83 A, each generator 115.21 A. (ii) IfI_f = 443.57 A; G1 and G4 supply 95.16 A each, G2 and G3 supply 126.62 A each.