Fault through impedance at bus 2

Short answer

Thevenin impedance at bus 2 is j0.5788 pu. With Z_f = j0.088 pu, fault current = 1.50 pu = 157.4 A at 110 kV. G1 supplies 0.883 pu (927 A) and G2 supplies 0.616 pu (647 A) at 11 kV, lagging by 90°.

In the power system shown in figure below, the value marked are the per unit reactance taking 20 MVA and 11 kV as base values in the generator circuit. Both the transformers are rated for 11/110 kV. A three phase to ground fault with a fault impedance of 0.088 pu occurs at bus 2. Determine the actual values of fault current and the currents supplied by the generators. [Figure: G1 (XG1 = 0.15) - T1 (j0.1) - bus 1; G2 (XG2 = j0.15) - T2 (j0.225) - bus 3; line 1-3 j0.5; line 1-2 0.75; line 3-2 1.0]

The fault current is found from the Thevenin (driving point) impedance at bus 2, If=Vf/(Z22+Zf)I_f = V_f/(Z_{22}+Z_f), with prefault voltage 1 pu. Bus voltages during the fault then give the generator currents.

Assumptions: all values are reactances (lines 1-2 = j0.75 and 3-2 = j1.0 pu), Zf=j0.088Z_f = j0.088 pu, no prefault load, prefault voltage 1 pu everywhere. Base: 20 MVA, 11 kV (generator side), so 110 kV on the line side.

Step 1: Reactance network

Generator + transformer branches: bus 1 to reference =0.15+0.10=0.25= 0.15 + 0.10 = 0.25; bus 3 to reference =0.15+0.225=0.375= 0.15 + 0.225 = 0.375.

      (ref)               (ref)
        |                   |
      j0.25               j0.375
        |                   |
  bus 1 o------j0.5---------o bus 3
         \                 /
        j0.75           j1.0
           \             /
            o---- bus 2 (fault, Zf=j0.088)

Step 2: Bus admittance matrix and Z-bus (values of −j-j / jj dropped, all reactive)

Ybus=−j[4+2+1.333−1.333−2−1.3331.333+1−1−2−12.667+2+1]=−j[7.333−1.333−2−1.3332.333−1−2−15.667]Y_{bus} = -j\begin{bmatrix} 4+2+1.333 & -1.333 & -2 \\ -1.333 & 1.333+1 & -1 \\ -2 & -1 & 2.667+2+1 \end{bmatrix} = -j\begin{bmatrix} 7.333 & -1.333 & -2 \\ -1.333 & 2.333 & -1 \\ -2 & -1 & 5.667 \end{bmatrix}

Inverting:

Zbus=j[0.18840.14730.09250.14730.57880.15410.09250.15410.2363]Z_{bus} = j\begin{bmatrix} 0.1884 & 0.1473 & 0.0925 \\ 0.1473 & 0.5788 & 0.1541 \\ 0.0925 & 0.1541 & 0.2363 \end{bmatrix}

So the Thevenin impedance at bus 2 is Z22=j0.5788Z_{22} = j0.5788 pu.

Step 3: Fault current

If=1Z22+Zf=1j(0.5788+0.088)=−j1.4998 puIb,110=20×1063×110×103=104.97 A∣If∣=1.4998×104.97=157.4 A\begin{aligned} I_f &= \frac{1}{Z_{22}+Z_f} = \frac{1}{j(0.5788+0.088)} = -j1.4998\ \text{pu} \\ I_{b,110} &= \frac{20\times10^6}{\sqrt3 \times 110\times10^3} = 104.97\ \text{A} \\ |I_f| &= 1.4998 \times 104.97 = 157.4\ \text{A} \end{aligned}

Step 4: Bus voltages during fault (Vi=1−Zi2IfV_i = 1 - Z_{i2} I_f)

V1=1−0.1473×1.4998=0.7791 puV2=1−0.5788×1.4998=0.1320 puV3=1−0.1541×1.4998=0.7689 pu\begin{aligned} V_1 &= 1 - 0.1473 \times 1.4998 = 0.7791\ \text{pu} \\ V_2 &= 1 - 0.5788 \times 1.4998 = 0.1320\ \text{pu} \\ V_3 &= 1 - 0.1541 \times 1.4998 = 0.7689\ \text{pu} \end{aligned}

Check: V2=ZfIf=0.088×1.4998=0.132V_2 = Z_f I_f = 0.088 \times 1.4998 = 0.132 pu.

Step 5: Generator currents

IG1=1−V10.25=0.22090.25=0.8834 puIG2=1−V30.375=0.23110.375=0.6163 pu\begin{aligned} I_{G1} &= \frac{1 - V_1}{0.25} = \frac{0.2209}{0.25} = 0.8834\ \text{pu} \\ I_{G2} &= \frac{1 - V_3}{0.375} = \frac{0.2311}{0.375} = 0.6163\ \text{pu} \end{aligned}

Check: 0.8834+0.6163=1.4997≈If0.8834 + 0.6163 = 1.4997 \approx I_f.

Generator currents flow on the 11 kV side, base current Ib,11=20×106/(3×11×103)=1049.7I_{b,11} = 20\times10^6/(\sqrt3 \times 11\times10^3) = 1049.7 A:

IG1=0.8834×1049.7=927.4 A,IG2=0.6163×1049.7=647.0 AI_{G1} = 0.8834 \times 1049.7 = 927.4\ \text{A}, \qquad I_{G2} = 0.6163 \times 1049.7 = 647.0\ \text{A}

Answer: Fault current at bus 2 = 1.50 pu = 157.4 A (110 kV side); G1 supplies 0.883 pu = 927 A and G2 supplies 0.616 pu = 647 A (11 kV side), all lagging the prefault voltage by 90°.