- 2071 Shrawan · 8 marks
Fault through impedance at bus 2
Short answer
Thevenin impedance at bus 2 is j0.5788 pu. With Z_f = j0.088 pu, fault current = 1.50 pu = 157.4 A at 110 kV. G1 supplies 0.883 pu (927 A) and G2 supplies 0.616 pu (647 A) at 11 kV, lagging by 90°.
In the power system shown in figure below, the value marked are the per unit reactance taking 20 MVA and 11 kV as base values in the generator circuit. Both the transformers are rated for 11/110 kV. A three phase to ground fault with a fault impedance of 0.088 pu occurs at bus 2. Determine the actual values of fault current and the currents supplied by the generators. [Figure: G1 (XG1 = 0.15) - T1 (j0.1) - bus 1; G2 (XG2 = j0.15) - T2 (j0.225) - bus 3; line 1-3 j0.5; line 1-2 0.75; line 3-2 1.0]
The fault current is found from the Thevenin (driving point) impedance at bus 2, , with prefault voltage 1 pu. Bus voltages during the fault then give the generator currents.
Assumptions: all values are reactances (lines 1-2 = j0.75 and 3-2 = j1.0 pu), pu, no prefault load, prefault voltage 1 pu everywhere. Base: 20 MVA, 11 kV (generator side), so 110 kV on the line side.
Step 1: Reactance network
Generator + transformer branches: bus 1 to reference ; bus 3 to reference .
(ref) (ref)
| |
j0.25 j0.375
| |
bus 1 o------j0.5---------o bus 3
\ /
j0.75 j1.0
\ /
o---- bus 2 (fault, Zf=j0.088)
Step 2: Bus admittance matrix and Z-bus (values of / dropped, all reactive)
Inverting:
So the Thevenin impedance at bus 2 is pu.
Step 3: Fault current
Step 4: Bus voltages during fault ()
Check: pu.
Step 5: Generator currents
Check: .
Generator currents flow on the 11 kV side, base current A:
Answer: Fault current at bus 2 = 1.50 pu = 157.4 A (110 kV side); G1 supplies 0.883 pu = 927 A and G2 supplies 0.616 pu = 647 A (11 kV side), all lagging the prefault voltage by 90°.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Generator-reactor system fault MVA · Power System Analysis II, chapter 3
- L-G fault at bus 1 through Zf · Power System Analysis II, chapter 5
- Short circuit MVA of feeder circuit breaker · Power System Analysis II, chapter 3 · asked 2×
- Neutral reactance for 15 MVA generator · Power System Analysis II, chapter 5
- L-L fault through Zf with two motors · Power System Analysis II, chapter 5
- Fault MVA at bus 5 with inductive lines · Power System Analysis II, chapter 3 · asked 2×
- Per unit circuit of three-generator system, 30 MVA base · Power System Analysis I, chapter 3
- Reactance diagram: 20 MVA generator, 15 kV/25 MVA base · Power System Analysis I, chapter 3
- Per unit values: 100 MVA generator, two motors · Power System Analysis I, chapter 3
- Reactance diagram: 300 MVA, 20 kV generator, two motors · Power System Analysis I, chapter 3