Power by two generators, 1.05∠5° and 1.05∠20° pu
Short answer
Total series impedance is 0.025+j0.26 pu and I from E1 to E2 is 1.0494 angle -162.01 pu. G2 generates 1.1012 pu real power while G1 absorbs 1.0737 pu, with 0.0275 pu line loss. G1 supplies 0.2477 pu reactive and G2 supplies 0.0386 pu reactive; real power flows from G2 to G1.
Determine the amount of power generated by each of the generators in the power system network below. Also specify the direction of power flow in the network. [Figure: E1 = 1.05∠5° pu behind reactance j0.08 pu, connected through a line of resistance 0.025 pu and reactance j0.1 pu to E2 = 1.05∠20° pu behind reactance j0.08 pu.]
The two internal reactances and the line form one series path between the two emfs:
Let I flow from to . Then is the power generated by G1 and is the power absorbed by G2.
j0.08 0.025+j0.1 j0.08
+-/\/\/-----/\/\/-------/\/\/-+
| I --> |
(E1) 1.05/5 deg 1.05/20 deg (E2)
| |
+-----------------------------+
Current
Powers
| Generator | Real power | Reactive power |
|---|---|---|
| G1 | absorbs 1.0737 pu (acts as motor) | generates 0.2477 pu |
| G2 | generates 1.1012 pu | generates 0.0386 pu |
Check: pu (I²R loss) and pu (I²X).
Direction of power flow
- Real power flows from G2 to G1, since leads by 15°.
- Both generators supply reactive power to the network, and it is consumed in the series reactances. With equal emf magnitudes, each machine supplies part of the .
Answer: G2 generates 1.101 pu real power and G1 receives 1.074 pu. The loss is 0.0275 pu. G1 and G2 supply 0.248 pu and 0.039 pu reactive power. P flows G2 → G1.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Power by two generators, 1.1∠15° and 1.1∠0° pu · Power System Analysis I, chapter 3 · asked 2×
- Reactance diagram: two generators, two motors, j50 Ω line · Power System Analysis I, chapter 3
- Reactance diagram: three generators, two 220 kV lines · Power System Analysis I, chapter 3
- Two sources via 0 - j5 Ω: power flow · Power System Analysis I, chapter 3
- Reactance diagram: 300 MVA, 20 kV generator, two motors · Power System Analysis I, chapter 3
- Reactance diagram: 50 MVA, 13.8 kV base, three generators · Power System Analysis I, chapter 3
- Vs from P+jQ and reactive power flow direction · Power System Analysis I, chapter 6
- N-R first iteration, line reactance 0.1 · Power System Analysis II, chapter 2
- G-S two iterations, lines 0.02+j0.11 · Power System Analysis II, chapter 2
- G-S two iterations, lines 0.026+j0.11 · Power System Analysis II, chapter 2
- Neutral reactance/resistance to limit L-G current · Power System Analysis II, chapter 5