Two sources via 0 - j5 Ω: power flow

Short answer

Current is 10.35∠15° A. Real power 1000 W flows from machine 1 to machine 2. Both machines absorb 267.95 var each; the capacitive line supplies 535.9 var.

Two ideal voltage sources designated as machines 1 and 2 are connected to each other via a line with impedance of 0 - j5 Ω. If E1 = 100∠0° V and E2 = 100∠30° V, determine the magnitude and the direction of power flow.

The line impedance Z=0−j5 ΩZ = 0 - j5\ \Omega is a pure capacitive reactance. Let I flow from machine 1 to machine 2. Then S1=E1I∗S_1 = E_1I^* is the power supplied by machine 1 and S2=E2I∗S_2 = E_2I^* is the power received by machine 2.

Current

E1−E2=100−(86.60+j50)=13.40−j50I=13.40−j50−j5=10+j2.679=10.353∠15∘ A\begin{aligned} E_1 - E_2 &= 100 - (86.60 + j50) = 13.40 - j50\\ I &= \frac{13.40 - j50}{-j5} = 10 + j2.679 = 10.353\angle15^\circ\ \text{A} \end{aligned}

Powers

S1=E1I∗=100(10−j2.679)=1000−j267.95 VAS2=E2I∗=(100∠30∘)(10.353∠−15∘)=1000+j267.95 VASZ=∣I∣2Z=107.18(−j5)=−j535.90 VA\begin{aligned} S_1 &= E_1I^* = 100(10 - j2.679) = 1000 - j267.95\ \text{VA}\\ S_2 &= E_2I^* = (100\angle30^\circ)(10.353\angle-15^\circ) = 1000 + j267.95\ \text{VA}\\ S_Z &= |I|^2Z = 107.18(-j5) = -j535.90\ \text{VA} \end{aligned}

Check with P=∣E1∣∣E2∣Xsin⁡(δ1−δ2)P = \frac{|E_1||E_2|}{X}\sin(\delta_1 - \delta_2) using X=−5X = -5: P=100×100−5sin⁡(−30∘)=+1000P = \frac{100\times100}{-5}\sin(-30^\circ) = +1000 W, from 1 to 2.

Magnitude and direction

QuantityResult
Real power1000 W flows from machine 1 to machine 2 (1 generates, 2 consumes)
Machine 1 reactiveQ1=−267.95Q_1 = -267.95 var, so it absorbs 267.95 var
Machine 2 reactivereceives +267.95 var, so it absorbs 267.95 var
Capacitive linegenerates 535.90 var (= 267.95 + 267.95)

Note: with an inductive link, real power flows from the leading machine (2) to the lagging one. A capacitive link reverses this, so power flows from machine 1 to machine 2 even though E2E_2 leads. The line capacitance supplies reactive power equally to both ends, because the voltage magnitudes are equal.

Answer: P = 1000 W flows from machine 1 to machine 2. Each machine absorbs 267.95 var, all supplied by the capacitive line (535.9 var).

✓ Answer checked by Claude Opus 5.5 (high effort)

All Power System Analysis I chapter 3 questions →