Reactive power flow between machines via j10 Ω

Short answer

With equal voltage magnitudes, reactive power flows from both machines into the inductive link: each supplies 241.2 var per phase, and the link loses 482.5 var per phase (1447.4 var three-phase). Real power flows from machine B to machine A at 1368.1 W per phase.

Two 3-phase synchronous machines are connected by an inductive link of j10 Ohms/phase. If the emfs of machine A and machine B are VA = 200∠10° V, VB = 200∠30° V, determine the direction of the reactive power flow and reactive power loss in the link. Neglect the voltage drops at both the machines.

Per phase, with I flowing from A to B through Z=j10 ΩZ = j10\ \Omega. Then SA=VAI∗S_A = V_AI^* is the power supplied by A and SB=VBI∗S_B = V_BI^* is the power received by B.

Current

VA=200∠10∘=196.96+j34.73 VVB=200∠30∘=173.21+j100.00 VI=VA−VBj10=23.76−j65.27j10=−6.527−j2.376=6.946∠−160∘ A\begin{aligned} V_A &= 200\angle10^\circ = 196.96 + j34.73\ \text{V}\\ V_B &= 200\angle30^\circ = 173.21 + j100.00\ \text{V}\\ I &= \frac{V_A - V_B}{j10} = \frac{23.76 - j65.27}{j10} = -6.527 - j2.376\\ &= 6.946\angle-160^\circ\ \text{A} \end{aligned}

Powers

SA=VAI∗=(200∠10∘)(6.946∠160∘)=−1368.08+j241.23 VASB=VBI∗=(200∠30∘)(6.946∠160∘)=−1368.08−j241.23 VAQloss=∣I∣2X=48.246×10=482.46 var\begin{aligned} S_A &= V_AI^* = (200\angle10^\circ)(6.946\angle160^\circ) = -1368.08 + j241.23\ \text{VA}\\ S_B &= V_BI^* = (200\angle30^\circ)(6.946\angle160^\circ) = -1368.08 - j241.23\ \text{VA}\\ Q_{loss} &= |I|^2X = 48.246\times10 = 482.46\ \text{var} \end{aligned}

Check: Qloss=∣VA−VB∣2X=(2×200sin⁡10∘)210=69.46210=482.46Q_{loss} = \frac{|V_A - V_B|^2}{X} = \frac{(2\times200\sin10^\circ)^2}{10} = \frac{69.46^2}{10} = 482.46 var.

Direction of reactive power

  • Machine A supplies +241.23 var into the link.
  • Machine B receives −241.23 var, so it also supplies 241.23 var into the link.
  • So reactive power flows from both ends into the link. There is no net transfer of vars from one machine to the other, because the voltage magnitudes are equal (200 V each). Each machine supplies half of the link's I2XI^2X.
  • Real power: 1368.08 W per phase flows from B (leading, 30°) to A (lagging, 10°).
QuantityPer phaseThree-phase
Q supplied by A241.23 var723.69 var
Q supplied by B241.23 var723.69 var
Reactive loss in link482.46 var1447.38 var
Real power B → A1368.08 W4104.24 W

Answer: Reactive power flows from both machines into the link, 241.2 var each per phase. The reactive loss in the link is 482.5 var per phase (1447.4 var for three phases).