Two machines 3.81∠0° and 3.81∠-18° kV

Short answer

Use I=(V1-V2)/Z; active power flows from machine 1 to machine 2. Three-phase: machine 1 generates 1293.3 kW, machine 2 consumes 1175.9 kW, line loss 117.3 kW. Reactive power flows from machine 2 to machine 1: machine 2 supplies 565.9 kvar, machine 1 receives 174.8 kvar, line absorbs 391.1 kvar.

Two 50 Hz, 3-phase synchronous machines are connected to each other via a line with series impedance of 3 + j10 Ohm/phase. Determine the direction of active and reactive power flow in the line and power generated/consumed by each of these machines. The terminal phase voltages of machines 1 and 2 are 3.81∠0° kV and 3.81∠-18° kV respectively.

Let I flow from machine 1 to machine 2 through Z=3+j10 ΩZ = 3 + j10\ \Omega. Then S1=V1I∗S_1 = V_1I^* is the power delivered by machine 1 and S2=V2I∗S_2 = V_2I^* is the power received by machine 2 (per phase; three-phase = 3 × per phase).

Current

V1=3810∠0∘ VV2=3810∠−18∘=3623.53−j1177.35 VI=V1−V2Z=186.47+j1177.353+j10=113.15+j15.30=114.18∠7.70∘ A\begin{aligned} V_1 &= 3810\angle0^\circ\ \text{V}\\ V_2 &= 3810\angle-18^\circ = 3623.53 - j1177.35\ \text{V}\\ I &= \frac{V_1 - V_2}{Z} = \frac{186.47 + j1177.35}{3 + j10}\\ &= 113.15 + j15.30 = 114.18\angle7.70^\circ\ \text{A} \end{aligned}

Powers per phase

S1=V1I∗=3810(113.15−j15.30)=431.09−j58.28 kVAS2=V2I∗=(3810∠−18∘)(114.18∠−7.70∘)=391.98−j188.64 kVASline=∣I∣2Z=13036.1(3+j10)=39.11+j130.36 kVA\begin{aligned} S_1 &= V_1I^* = 3810(113.15 - j15.30) = 431.09 - j58.28\ \text{kVA}\\ S_2 &= V_2I^* = (3810\angle-18^\circ)(114.18\angle-7.70^\circ) = 391.98 - j188.64\ \text{kVA}\\ S_{line} &= |I|^2Z = 13036.1(3 + j10) = 39.11 + j130.36\ \text{kVA} \end{aligned}

Check: 431.09−391.98=39.11431.09 - 391.98 = 39.11 kW and 188.64−58.28=130.36188.64 - 58.28 = 130.36 kvar.

Results

QuantityPer phaseThree-phase
Machine 1, Pgenerates 431.09 kW1293.26 kW
Machine 1, QQ1=−58.28Q_1 = -58.28, so it absorbs 58.28 kvar174.84 kvar
Machine 2, Pconsumes 391.98 kW (motor)1175.94 kW
Machine 2, Qreceives −188.64, so it generates 188.64 kvar565.92 kvar
Line loss39.11 kW, 130.36 kvar117.33 kW, 391.08 kvar

Direction of flow

  • Active power flows from machine 1 to machine 2, because V1V_1 leads V2V_2 by 18°.
  • Reactive power flows from machine 2 towards machine 1. Machine 2 supplies 188.64 kvar: 130.36 kvar is used in the line reactance and 58.28 kvar reaches machine 1. Both voltage magnitudes are equal, so the flow of Q depends on the angle and on the line resistance.

Answer: Machine 1 is the generator (1293.3 kW, three-phase) and machine 2 the motor (1175.9 kW). The line loss is 117.3 kW. Q flows from machine 2 (565.9 kvar) to machine 1 (174.8 kvar received). The line absorbs 391.1 kvar.