- 2069 Poush · 6 marks
Two machines 3.81∠0° and 3.81∠-18° kV
Short answer
Use I=(V1-V2)/Z; active power flows from machine 1 to machine 2. Three-phase: machine 1 generates 1293.3 kW, machine 2 consumes 1175.9 kW, line loss 117.3 kW. Reactive power flows from machine 2 to machine 1: machine 2 supplies 565.9 kvar, machine 1 receives 174.8 kvar, line absorbs 391.1 kvar.
Two 50 Hz, 3-phase synchronous machines are connected to each other via a line with series impedance of 3 + j10 Ohm/phase. Determine the direction of active and reactive power flow in the line and power generated/consumed by each of these machines. The terminal phase voltages of machines 1 and 2 are 3.81∠0° kV and 3.81∠-18° kV respectively.
Let I flow from machine 1 to machine 2 through . Then is the power delivered by machine 1 and is the power received by machine 2 (per phase; three-phase = 3 × per phase).
Current
Powers per phase
Check: kW and kvar.
Results
| Quantity | Per phase | Three-phase |
|---|---|---|
| Machine 1, P | generates 431.09 kW | 1293.26 kW |
| Machine 1, Q | , so it absorbs 58.28 kvar | 174.84 kvar |
| Machine 2, P | consumes 391.98 kW (motor) | 1175.94 kW |
| Machine 2, Q | receives −188.64, so it generates 188.64 kvar | 565.92 kvar |
| Line loss | 39.11 kW, 130.36 kvar | 117.33 kW, 391.08 kvar |
Direction of flow
- Active power flows from machine 1 to machine 2, because leads by 18°.
- Reactive power flows from machine 2 towards machine 1. Machine 2 supplies 188.64 kvar: 130.36 kvar is used in the line reactance and 58.28 kvar reaches machine 1. Both voltage magnitudes are equal, so the flow of Q depends on the angle and on the line resistance.
Answer: Machine 1 is the generator (1293.3 kW, three-phase) and machine 2 the motor (1175.9 kW). The line loss is 117.3 kW. Q flows from machine 2 (565.9 kvar) to machine 1 (174.8 kvar received). The line absorbs 391.1 kvar.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Reactive power flow between machines via j10 Ω · Power System Analysis I, chapter 3
- Direction of active and reactive power flow · Power System Analysis I, chapter 6
- Two machines 11∠0° and 11∠40° kV via j15 Ω · Power System Analysis I, chapter 3
- Active power between machines, 200∠0° and 200∠15° V · Power System Analysis I, chapter 3
- Two sources via 0 - j5 Ω: power flow · Power System Analysis I, chapter 3
- Two machines 100∠0° and 120∠30° V via j5 Ω · Power System Analysis I, chapter 3
- Delta connected coils line current and power · Basic Electrical Engineering, chapter 8