Two machines 11∠0° and 11∠40° kV via j15 Ω

Short answer

With per-phase EMFs 6.351∠0° kV and 6.351∠40° kV, line current I = (E1-E2)/j15 = 289.6∠-160° A. Machine 1 consumes 5.185 MW (motor) and supplies 1.887 Mvar; machine 2 generates 5.185 MW (generator) and also supplies 1.887 Mvar. Total line reactive absorption is 3.774 Mvar.

Two three-phase machines have generated EMF of 11∠0° kV and 11∠40° kV. They are connected through a 3-phase line having an impedance of 0 + j15 Ω per phase. Find: (i) whether each machine is acting as generator or motor and the real power generated or consumed by them; (ii) whether each machine is delivering or consuming reactive power and the amount of reactive power.

Assumption: 11 kV is the line-to-line EMF. The per-phase EMFs are therefore E1=6.351∠0∘E_1 = 6.351\angle0^\circ kV and E2=6.351∠40∘E_2 = 6.351\angle40^\circ kV. The current II is taken as flowing from machine 1 to machine 2 through Z=j15 ΩZ = j15\ \Omega.

Current

I=E1−E2jX=6351∠0∘−6351∠40∘j15=289.6∠−160∘ A\begin{aligned} I &= \frac{E_1 - E_2}{jX} = \frac{6351\angle0^\circ - 6351\angle40^\circ}{j15}\\ &= 289.6\angle-160^\circ\ \text{A} \end{aligned}

Complex power (three-phase)

Machine 1, with power taken out of its terminal:

S1=3E1I∗=−5.185+j1.887 MVAS_1 = 3E_1I^* = -5.185 + j1.887\ \text{MVA}

Machine 2, with power taken into it (since II enters it):

S2=3E2I∗=−5.185−j1.887 MVAS_2 = 3E_2I^* = -5.185 - j1.887\ \text{MVA}

Check with the standard formulas:

P=E1E2sin⁡δX=11×11×sin⁡40∘15=5.185 MWQ=E2(1−cos⁡δ)X=121(1−cos⁡40∘)15=1.887 Mvar\begin{aligned} P &= \frac{E_1E_2\sin\delta}{X} = \frac{11\times11\times\sin40^\circ}{15} = 5.185\ \text{MW}\\ Q &= \frac{E^2(1-\cos\delta)}{X} = \frac{121(1-\cos40^\circ)}{15} = 1.887\ \text{Mvar} \end{aligned}

(i) Real power

  • Machine 1: P1=−5.185P_1 = -5.185 MW out of it, so it consumes 5.185 MW and acts as a motor.
  • Machine 2: P2,in=−5.185P_{2,in} = -5.185 MW, so it generates 5.185 MW and acts as a generator.

Machine 2's EMF leads by 40°, so real power flows from 2 to 1. The line is lossless (R=0R = 0), so the two powers are equal.

(ii) Reactive power

  • Machine 1: Q1=+1.887Q_1 = +1.887 Mvar out of it, so it delivers 1.887 Mvar.
  • Machine 2: Q2,in=−1.887Q_{2,in} = -1.887 Mvar, so it also delivers 1.887 Mvar.

Both machines supply reactive power to the line, which absorbs:

3∣I∣2X=3×289.62×15=3.774 Mvar3|I|^2X = 3\times289.6^2\times15 = 3.774\ \text{Mvar}

Answer: Machine 1 is a motor consuming 5.185 MW, and machine 2 is a generator producing 5.185 MW. Each machine supplies 1.887 Mvar, a total of 3.774 Mvar absorbed by the line reactance.