- 2071 Magh · 5 marks
Two machines 100∠0° and 120∠30° V via j5 Ω
Short answer
Current I = 12.03∠176.3° A. Real power 1200 W per phase flows from B to A (B generates, A motors). Reactive power: B supplies 801.5 var, line absorbs 723.1 var, A receives 78.5 var per phase.
Two ideal 3-phase synchronous machines A and B are connected by a series impedance of 0 + j5 Ω per phase. The voltages at the two machines are 100∠0° and 120∠30° V respectively. Calculate and analyze the direction of power flow in the system.
Take the voltages as per-phase values. Let I flow from A to B. Then is the power supplied by A and is the power received by B.
Current
Powers per phase
Check with the lossless-line formula: W.
Analysis
| Machine | Real power | Reactive power |
|---|---|---|
| A | supplies −1200 W, so it receives 1200 W (motor) | supplies −78.46 var, so it receives 78.46 var |
| B | receives −1200 W, so it generates 1200 W | receives −801.54 var, so it supplies 801.54 var |
| Link (j5 Ω) | 0 W (no resistance) | absorbs 723.08 var |
- Real power flows from B to A because leads by 30°. There is no resistance, so A receives exactly what B sends.
- Reactive power flows from B (higher voltage, 120 V) to A (lower voltage, 100 V). B supplies 801.54 var: 723.08 var is used in the link and 78.46 var reaches A.
- Three-phase totals (×3): 3600 W from B to A; B supplies 2404.6 var; the link absorbs 2169.2 var; A receives 235.4 var.
Answer: B is the generator and sends 1200 W per phase (3.6 kW total) to A, which acts as a motor. Q flows from B to A: B supplies 801.5 var, the link uses 723.1 var, and A receives 78.5 var (per phase).
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Two sources via 0 - j5 Ω: power flow · Power System Analysis I, chapter 3
- Two sources 120∠10° and 120∠30° V via 1+j5 Ω · Power System Analysis I, chapter 3
- Reactive power flow between machines via j10 Ω · Power System Analysis I, chapter 3
- Two machines 3.81∠0° and 3.81∠-18° kV · Power System Analysis I, chapter 3
- Active power between machines, 200∠0° and 200∠15° V · Power System Analysis I, chapter 3
- Two machines 11∠0° and 11∠40° kV via j15 Ω · Power System Analysis I, chapter 3
- Series capacitor to limit power angle to 30° · Power System Analysis II, chapter 6