Series capacitor to limit power angle to 30°
Short answer
With E = V = 1 pu, the total reactance for 1 pu power at 30° must be 0.5 pu. The uncompensated reactance is 1.0 pu, so a series capacitor of 0.5 pu (174.24 Ω, ~18.27 μF per phase at 50 Hz) is needed.
For a synchronous generator connected to infinite bus as shown in figure below, compute the value of series capacitor so that the power angle at steady state could be limited to 30° for generator supplying power of 1 p.u. [Figure: generator 6.6 kV, 50 MVA, 0.3 p.u (Y grounded) - transformer 6.6/132 kV, 50 MVA, 0.1 p.u - line j0.3 - series capacitor −jXc - line j0.3 - 132 kV infinite bus]
Assumptions: the generator internal emf is not given, so pu is assumed, with infinite bus voltage pu. The base is 50 MVA, 132 kV on the line side.
Data (pu on 50 MVA): , , line sections , series capacitor .
Step 1: Required total reactance
Step 2: Capacitor reactance
Uncompensated reactance: pu. So
Without the capacitor, , giving , which is right at the limit. The capacitor is therefore essential.
Step 3: Actual value
Answer: pu = 174.24 Ω per phase, i.e. F per phase (50% compensation of the total reactance).
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Critical clearing angle/time, fault at infinite bus · Power System Analysis II, chapter 6
- Rotor angle and swing equation, infinite bus · Power System Analysis II, chapter 6
- Power angle and series compensation · Power System Analysis II, chapter 6
- L-G fault and 3-phase fault, 30 MVA generator · Power System Analysis II, chapter 5
- Neutral reactance for 15 MVA generator · Power System Analysis II, chapter 5
- Critical clearing, fault at infinite bus, H = 6 · Power System Analysis II, chapter 6
- Reactance diagram: 30 MVA, 6.6 kV base, three lines · Power System Analysis I, chapter 3
- Bus-bar reactor scheme: 30 MVA and 50 MVA · Power Plant Equipment, chapter 4 · asked 2×
- Reactance diagram: 50 MVA, 13.8 kV base, three generators · Power System Analysis I, chapter 3
- Reactance diagram: 300 MVA, 20 kV generator, two motors · Power System Analysis I, chapter 3