Power angle and series compensation

Short answer

The power angle is 53.13°. To reduce it to 30°, a series capacitor of XC = 0.3 pu (37.5% compensation) is required.

A transmission line connecting a generator to an infinite bus has a series reactance of 0.8 p.u. Assuming the sending and receiving end voltage are at 1 p.u. each compute the following: i. Power angle if the line delivers a 1 p.u. power to infinite bus ii. Series compensation required to bring the power angle to 30°.

For a lossless line, P=VSVRXsin⁡δP = \dfrac{V_SV_R}{X}\sin\delta. Series capacitors reduce the net reactance XX. For the same power, this reduces δ\delta and raises the stability margin.

Data: XL=0.8X_L = 0.8 pu, VS=VR=1V_S = V_R = 1 pu, P=1P = 1 pu.

(i) Power angle without compensation

sin⁡δ=PXLVSVR=1×0.81×1=0.8δ=sin⁡−10.8=53.13∘\begin{aligned} \sin\delta &= \frac{PX_L}{V_SV_R} = \frac{1\times0.8}{1\times1} = 0.8 \\ \delta &= \sin^{-1}0.8 = 53.13^\circ \end{aligned}

(ii) Series compensation for δ=30∘\delta = 30^\circ

The net reactance needed is

Xnet=VSVRsin⁡30∘P=1×1×0.51=0.5 puX_{net} = \frac{V_SV_R\sin30^\circ}{P} = \frac{1\times1\times0.5}{1} = 0.5\ \text{pu}

So the series capacitor must have

XC=XL−Xnet=0.8−0.5=0.3 puX_C = X_L - X_{net} = 0.8 - 0.5 = 0.3\ \text{pu} Degree of compensation=XCXL×100=0.30.8×100=37.5%\text{Degree of compensation} = \frac{X_C}{X_L}\times100 = \frac{0.3}{0.8}\times100 = 37.5\%

Effect on stability

QuantityUncompensatedCompensated
Net XX (pu)0.80.5
PmaxP_{max} (pu)1.252.0
δ\delta for 1 pu53.13°30°
Steady-state margin20%50%

Answer: (i) δ=53.13∘\delta = 53.13^\circ; (ii) series capacitive reactance XC=0.3X_C = 0.3 pu, i.e. 37.5% series compensation.