- 2069 Chaitra · 5+5 marks
Power angle and series compensation
Short answer
The power angle is 53.13°. To reduce it to 30°, a series capacitor of XC = 0.3 pu (37.5% compensation) is required.
A transmission line connecting a generator to an infinite bus has a series reactance of 0.8 p.u. Assuming the sending and receiving end voltage are at 1 p.u. each compute the following: i. Power angle if the line delivers a 1 p.u. power to infinite bus ii. Series compensation required to bring the power angle to 30°.
For a lossless line, . Series capacitors reduce the net reactance . For the same power, this reduces and raises the stability margin.
Data: pu, pu, pu.
(i) Power angle without compensation
(ii) Series compensation for
The net reactance needed is
So the series capacitor must have
Effect on stability
| Quantity | Uncompensated | Compensated |
|---|---|---|
| Net (pu) | 0.8 | 0.5 |
| (pu) | 1.25 | 2.0 |
| for 1 pu | 53.13° | 30° |
| Steady-state margin | 20% | 50% |
Answer: (i) ; (ii) series capacitive reactance pu, i.e. 37.5% series compensation.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Series capacitor to limit power angle to 30° · Power System Analysis II, chapter 6
- Critical clearing for temporary sending-end fault · Power System Analysis II, chapter 6
- Critical clearing angle/time, fault at infinite bus · Power System Analysis II, chapter 6
- Rotor angle and swing equation, infinite bus · Power System Analysis II, chapter 6
- Fault at receiving end of 132 kV lines · Power System Analysis II, chapter 3
- Critical clearing angle, breakers 1 and 2 · Power System Analysis II, chapter 6 · asked 2×
- Static compensation to hold sending end at 140 kV · Power System Analysis I, chapter 6
- Expression for receiving-end shunt compensation · High Voltage Engineering, chapter 3
- Long line sending end voltage derivation · Power System Analysis I, chapter 5
- Receiving and sending end powers from ABCD, 132/134 kV · Power System Analysis I, chapter 6