Direction of active and reactive power flow

Short answer

Active power flows from the bus with leading phase angle to the lagging one, as P ∝ sinδ. Reactive power flows from higher voltage magnitude to lower, since Q ∝ (V₁ − V₂) for small angle differences.

"Direction of active power flow is from leading phase angle to lagging phase angle whereas direction of reactive power flow is from higher voltage magnitude to lower voltage magnitude." Verify the above statement with mathematical explanation and diagrams.

Consider two buses joined by a short line of reactance XX (resistance neglected, as X≫RX \gg R). Bus 1 voltage V1∠δ1V_1\angle\delta_1, bus 2 voltage V2∠δ2V_2\angle\delta_2, and δ=δ1−δ2\delta = \delta_1 - \delta_2.

  V1/_d1        jX         V2/_d2
   o-----------/\/\/----------o
   |      P, Q  -->           |
  Bus 1                     Bus 2

Derivation

I=V1∠δ1−V2∠δ2jXI = \frac{V_1\angle\delta_1 - V_2\angle\delta_2}{jX}

Power received at bus 2:

S2=V2∠δ2 I∗=V1V2sin⁡δX+j V1V2cos⁡δ−V22XS_2 = V_2\angle\delta_2\,I^* = \frac{V_1V_2\sin\delta}{X} + j\,\frac{V_1V_2\cos\delta - V_2^2}{X}

So

P=V1V2Xsin⁡δ,Q=V2X(V1cos⁡δ−V2)P = \frac{V_1V_2}{X}\sin\delta,\qquad Q = \frac{V_2}{X}\left(V_1\cos\delta - V_2\right)

Active power: from leading to lagging angle

  • PP depends on sin⁡δ\sin\delta. If δ1>δ2\delta_1 > \delta_2 (bus 1 leads), sin⁡δ>0\sin\delta > 0 and P>0P > 0: power flows from 1 to 2.
  • If bus 2 leads, P<0P < 0: power flows from 2 to 1.
  • PP flows even if V1=V2V_1 = V_2, as long as there is an angle difference.

Reactive power: from higher to lower magnitude

In practice δ\delta is small, so cos⁡δ≈1\cos\delta \approx 1:

Q≈V2(V1−V2)XQ \approx \frac{V_2(V_1 - V_2)}{X}
  • If ∣V1∣>∣V2∣|V_1| > |V_2|, Q>0Q > 0: reactive power flows from 1 to 2.
  • If ∣V1∣<∣V2∣|V_1| < |V_2|, QQ reverses.
  • It hardly depends on δ\delta.

Phasor illustration

Case A: P flow           Case B: Q flow
  V1 (leads)               V1 (longer)
   /                       ------------>
  / delta                  V2 (shorter, same angle)
 O-------> V2              ------->
 P: 1 -> 2                 Q: 1 -> 2

Example

X=10 ΩX = 10\ \Omega, V1=11∠5∘V_1 = 11\angle5^\circ kV, V2=10.5∠0∘V_2 = 10.5\angle0^\circ kV: P=11×10.510sin⁡5∘=1.01P = \frac{11\times10.5}{10}\sin5^\circ = 1.01 MW (1 → 2), Q=10.510(11cos⁡5∘−10.5)=0.48Q = \frac{10.5}{10}(11\cos5^\circ - 10.5) = 0.48 MVAr (1 → 2). If instead V2=11.5∠0∘V_2 = 11.5\angle0^\circ kV, PP still flows 1 → 2, but Q=11.510(11cos⁡5∘−11.5)=−0.62Q = \frac{11.5}{10}(11\cos5^\circ - 11.5) = -0.62 MVAr, i.e. Q flows 2 → 1.

Hence the statement is verified: P follows the phase angle, Q follows the voltage magnitude.

✓ Answer checked by Claude Opus 5.5 (high effort)