- 2069 Bhadra · 6 marks
Direction of active and reactive power flow
Short answer
Active power flows from the bus with leading phase angle to the lagging one, as P ∝ sinδ. Reactive power flows from higher voltage magnitude to lower, since Q ∝ (V₁ − V₂) for small angle differences.
"Direction of active power flow is from leading phase angle to lagging phase angle whereas direction of reactive power flow is from higher voltage magnitude to lower voltage magnitude." Verify the above statement with mathematical explanation and diagrams.
Consider two buses joined by a short line of reactance (resistance neglected, as ). Bus 1 voltage , bus 2 voltage , and .
V1/_d1 jX V2/_d2
o-----------/\/\/----------o
| P, Q --> |
Bus 1 Bus 2
Derivation
Power received at bus 2:
So
Active power: from leading to lagging angle
- depends on . If (bus 1 leads), and : power flows from 1 to 2.
- If bus 2 leads, : power flows from 2 to 1.
- flows even if , as long as there is an angle difference.
Reactive power: from higher to lower magnitude
In practice is small, so :
- If , : reactive power flows from 1 to 2.
- If , reverses.
- It hardly depends on .
Phasor illustration
Case A: P flow Case B: Q flow
V1 (leads) V1 (longer)
/ ------------>
/ delta V2 (shorter, same angle)
O-------> V2 ------->
P: 1 -> 2 Q: 1 -> 2
Example
, kV, kV: MW (1 → 2), MVAr (1 → 2). If instead kV, still flows 1 → 2, but MVAr, i.e. Q flows 2 → 1.
Hence the statement is verified: P follows the phase angle, Q follows the voltage magnitude.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Vs from P+jQ and reactive power flow direction · Power System Analysis I, chapter 6
- Reactive power flow between machines via j10 Ω · Power System Analysis I, chapter 3
- Reactive power proportional to voltage drop · Power System Analysis I, chapter 6
- Active power between machines, 200∠0° and 200∠15° V · Power System Analysis I, chapter 3
- Two sources via 0 - j5 Ω: power flow · Power System Analysis I, chapter 3
- Sending end active power from ABCD, 132/130.5 kV · Power System Analysis I, chapter 6
- Synchronous motor drawing lagging and leading current · Electric Machines II, chapter 2 · asked 4×
- T/F: single phase transformers for lower utilization voltage · Transmission and Distribution System Design, chapter 7
- Synchronous motor features and lagging/leading operation · Electric Machines II, chapter 2
- Consequences of higher or lower SCR · Power Plant Design, chapter 4 · asked 3×