- 2077 Chaitra · 4 marks
Sending end active power from ABCD, 132/130.5 kV
Short answer
Sending end active power is −27.63 MW, meaning 27.63 MW flows into the sending-end bus. Result from power-circle equation with VS=132 kV, VR=130.5∠10° kV, A=0.97∠0.5°, B=100∠75° Ω.
A 3-phase overhead line has the following parameters: VS = 132∠0° kV, VR = 130.5∠10° kV, A = 0.97∠0.5°, B = 100∠75° ohms/ph. Determine the sending end active power.
Use the sending-end power-circle equation (taking ). With line voltages in kV, the result is in three-phase MW:
Here is the angle by which leads . Since and ,
Data: , , , .
Substitution
Meaning
is negative because the receiving-end voltage leads the sending-end voltage by . Active power flows from the leading to the lagging end, so about 27.6 MW actually flows out of the line at the sending end (from the "receiving" bus towards the "sending" bus).
Answer: ≈ −27.63 MW (27.63 MW flows into the sending-end bus).
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Receiving and sending end powers from ABCD, 132/134 kV · Power System Analysis I, chapter 6
- 220 kV line, 200 MW: sending end from ABCD · Power System Analysis I, chapter 6
- Sending and receiving power, 140∠10° and 132 kV · Power System Analysis I, chapter 6
- Receiving end power, 140.2∠18.2° kV and 132 kV · Power System Analysis I, chapter 6
- Sending end from A = 0.98∠0.3°, B = 110∠75° · Power System Analysis I, chapter 6 · asked 2×
- Line power loss, 138.5∠8° kV and 132 kV · Power System Analysis I, chapter 6
- Shunt reactors for 750 kV line ABCD · High Voltage Engineering, chapter 3
- Conductor selection, 100 MW 70 km 132 kV · Transmission and Distribution System Design, chapter 4
- Fault at load end of overhead line · Power System Analysis II, chapter 3
- Fault at receiving end of 132 kV lines · Power System Analysis II, chapter 3