Sending end from A = 0.98∠0.3°, B = 110∠75°

Short answer

The sending-end line voltage is 164.27 kV with power angle 9.25°. Sending-end powers are 43.69 MW and 35.76 MVAr. Line losses are 3.69 MW and the line absorbs 5.76 MVAr.

A three phase 132 kV overhead line delivers 50 MVA at 132 kV and power factor 0.8 lagging at its receiving end. The constants of the line are A = 0.98∠0.3° and B = 110∠75° ohms per phase. Find (a) sending end voltage and power angle (b) sending end active and reactive power (c) line losses and VARs absorbed by the line.

Data: A=0.98∠0.3∘A = 0.98\angle0.3^\circ, B=110∠75∘ ΩB = 110\angle75^\circ\ \Omega, load 50 MVA at 0.8 lag at 132 kV, i.e. SR=40+j30S_R = 40 + j30 MVA. D=AD = A is assumed (symmetrical line).

(a) Sending-end voltage and power angle

VR=132/3=76.21∠0∘ kVIR=50×1063×132×103=218.69∠−36.87∘ AAVR=74.69∠0.3∘ kVBIR=110∠75∘×0.21869∠−36.87∘=24.06∠38.13∘ kVVS=AVR+BIR=94.84∠9.25∘ kV (phase)\begin{aligned} V_R &= 132/\sqrt3 = 76.21\angle0^\circ\ \text{kV} \\ I_R &= \frac{50\times10^6}{\sqrt3\times132\times10^3} = 218.69\angle-36.87^\circ\ \text{A} \\ AV_R &= 74.69\angle0.3^\circ\ \text{kV} \\ BI_R &= 110\angle75^\circ\times0.21869\angle-36.87^\circ = 24.06\angle38.13^\circ\ \text{kV} \\ V_S &= AV_R + BI_R = 94.84\angle9.25^\circ\ \text{kV (phase)} \end{aligned}

∣VS∣|V_S| (line) =3×94.84=164.27= \sqrt3\times94.84 = 164.27 kV, power angle δ=9.25∘\delta = 9.25^\circ.

(b) Sending-end active and reactive power

PS=∣A∣∣VS∣2∣B∣cos⁡(β−α)−∣VS∣∣VR∣∣B∣cos⁡(β+δ)QS=∣A∣∣VS∣2∣B∣sin⁡(β−α)−∣VS∣∣VR∣∣B∣sin⁡(β+δ)\begin{aligned} P_S &= \frac{|A||V_S|^2}{|B|}\cos(\beta-\alpha) - \frac{|V_S||V_R|}{|B|}\cos(\beta+\delta) \\ Q_S &= \frac{|A||V_S|^2}{|B|}\sin(\beta-\alpha) - \frac{|V_S||V_R|}{|B|}\sin(\beta+\delta) \end{aligned}

With 0.98×164.272110=240.41\frac{0.98\times164.27^2}{110} = 240.41, 164.27×132110=197.12\frac{164.27\times132}{110} = 197.12, β−α=74.7∘\beta-\alpha = 74.7^\circ, β+δ=84.25∘\beta+\delta = 84.25^\circ:

PS=240.41cos⁡74.7∘−197.12cos⁡84.25∘=43.69 MWQS=240.41sin⁡74.7∘−197.12sin⁡84.25∘=35.76 MVAr\begin{aligned} P_S &= 240.41\cos74.7^\circ - 197.12\cos84.25^\circ = 43.69\ \text{MW} \\ Q_S &= 240.41\sin74.7^\circ - 197.12\sin84.25^\circ = 35.76\ \text{MVAr} \end{aligned}

(Check with the receiving-end equations at δ=9.25∘\delta = 9.25^\circ: PR=40.00P_R = 40.00 MW, QR=30.00Q_R = 30.00 MVAr.)

(c) Line losses and VARs absorbed

Ploss=43.69−40=3.69 MWQabsorbed=35.76−30=5.76 MVAr\begin{aligned} P_{loss} &= 43.69 - 40 = 3.69\ \text{MW} \\ Q_{absorbed} &= 35.76 - 30 = 5.76\ \text{MVAr} \end{aligned}

Answer: (a) VSV_S = 164.27 kV, δ = 9.25°; (b) PSP_S = 43.69 MW, QSQ_S = 35.76 MVAr; (c) loss 3.69 MW, line absorbs 5.76 MVAr.

✓ Answer checked by Claude Opus 5.5 (high effort)