- 2068 Magh · 5 marks
Receiving end power, 140.2∠18.2° kV and 132 kV
Short answer
Using P_R = (|V_S||V_R|/|B|) cos(β−δ) − (|A||V_R|²/|B|) cos(β−α) with given ABCD parameters yields receiving-end active power of 90.2 MW.
For a 3-phase line the following data is available at a particular instant: VS (line) = 140.2∠18.2° kV, VR (line) = 132 kV∠0°, A = 0.94∠0.4°, B = 64.2∠78.8° Ohms. Compute the receiving end active power.
Use the receiving-end power-circle equation. With line kV, the result is three-phase MW:
Data: kV, , kV, , , , .
Substitution
Answer: Receiving-end active power ≈ 90.2 MW.
✓ Answer checked by Claude Opus 5.5 (high effort)