- 2070 Bhadra · 4 marks
Maximum power with 138.5∠8° kV and 132 kV
Short answer
Maximum active power is 346.7 MW, occurring when load angle equals 71.5°. At this condition, the receiving end must supply about 443.2 MVAr (leading reactive power).
For a 3-phase overhead line, the following data is available: VS,L = 138.5∠8° kV, VR,L = 132∠0° kV, A = 0.983∠0.68°, B = 36.5∠71.5° Ω. Determine the maximum amount of active power that can be delivered by the line. What will be the reactive power delivered at that condition?
For fixed voltage magnitudes, the receiving-end power
is maximum when . (Line kV give three-phase MW/MVAr.)
Data: kV, kV, , , , , so .
Maximum active power
Reactive power at this condition
At , :
The negative sign means the receiving end must supply about 443 MVAr to the line (the load must be strongly leading, pf ≈ 0.62 lead) for maximum power transfer. The load angle at this condition is .
Answer: ≈ 346.7 MW; reactive power at the receiving end ≈ −443.2 MVAr (443.2 MVAr must be supplied at the receiving end).
✓ Answer checked by Claude Opus 5.5 (high effort)