Maximum power with 132 kV at both ends

Short answer

Maximum deliverable power is 110.4 MW, with receiving-end power factor 0.599 leading and efficiency 59.6%.

A 132 kV, 3-phase transmission line has constants A = 0.98∠3° and B = 110∠75° ohms per phase. The line is to be operated with both sending end and receiving end voltages at 132 kV. Determine the maximum power which the line can deliver. What will be the power factor at the receiving end and efficiency of the line under this condition?

Data: ∣A∣=0.98|A| = 0.98, α=3∘\alpha = 3^\circ, ∣B∣=110 Ω|B| = 110\ \Omega, β=75∘\beta = 75^\circ, ∣VS∣=∣VR∣=132|V_S| = |V_R| = 132 kV. Take D=AD = A. Line kV give three-phase MW/MVAr.

Maximum power

Maximum PRP_R occurs at δ=β=75∘\delta = \beta = 75^\circ:

PR,max=∣VS∣∣VR∣∣B∣−∣A∣∣VR∣2∣B∣cos⁡(β−α)=1322110−0.98×1322110cos⁡72∘=158.40−155.23×0.3090=158.40−47.97=110.43 MW\begin{aligned} P_{R,max} &= \frac{|V_S||V_R|}{|B|} - \frac{|A||V_R|^2}{|B|}\cos(\beta-\alpha) \\ &= \frac{132^2}{110} - \frac{0.98\times132^2}{110}\cos72^\circ \\ &= 158.40 - 155.23\times0.3090 = 158.40 - 47.97 = 110.43\ \text{MW} \end{aligned}

Receiving-end power factor

QR=−∣A∣∣VR∣2∣B∣sin⁡(β−α)=−155.23sin⁡72∘=−147.63 MVArQ_R = -\frac{|A||V_R|^2}{|B|}\sin(\beta-\alpha) = -155.23\sin72^\circ = -147.63\ \text{MVAr} pfR=110.43110.432+147.632=0.599 leading\text{pf}_R = \frac{110.43}{\sqrt{110.43^2 + 147.63^2}} = 0.599\ \text{leading}

Efficiency

Sending-end power at δ=75∘\delta = 75^\circ (β+δ=150∘\beta+\delta = 150^\circ):

PS=∣A∣∣VS∣2∣B∣cos⁡(β−α)−∣VS∣∣VR∣∣B∣cos⁡(β+δ)=155.23cos⁡72∘−158.40cos⁡150∘=47.97+137.18=185.15 MW\begin{aligned} P_S &= \frac{|A||V_S|^2}{|B|}\cos(\beta-\alpha) - \frac{|V_S||V_R|}{|B|}\cos(\beta+\delta) \\ &= 155.23\cos72^\circ - 158.40\cos150^\circ \\ &= 47.97 + 137.18 = 185.15\ \text{MW} \end{aligned} η=110.43185.15×100=59.64%\eta = \frac{110.43}{185.15}\times100 = 59.64\%

The low efficiency shows that operating at the theoretical maximum (steady-state stability limit) is not practical.

Answer: PmaxP_{max} ≈ 110.4 MW, receiving-end pf ≈ 0.599 leading, efficiency ≈ 59.6 %.