- 2070 Magh · 6 marks
Maximum power with 132 kV at both ends
Short answer
Maximum deliverable power is 110.4 MW, with receiving-end power factor 0.599 leading and efficiency 59.6%.
A 132 kV, 3-phase transmission line has constants A = 0.98∠3° and B = 110∠75° ohms per phase. The line is to be operated with both sending end and receiving end voltages at 132 kV. Determine the maximum power which the line can deliver. What will be the power factor at the receiving end and efficiency of the line under this condition?
Data: , , , , kV. Take . Line kV give three-phase MW/MVAr.
Maximum power
Maximum occurs at :
Receiving-end power factor
Efficiency
Sending-end power at ():
The low efficiency shows that operating at the theoretical maximum (steady-state stability limit) is not practical.
Answer: ≈ 110.4 MW, receiving-end pf ≈ 0.599 leading, efficiency ≈ 59.6 %.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Sending end from A = 0.98∠0.3°, B = 110∠75° · Power System Analysis I, chapter 6 · asked 2×
- Sending end from A = 0.98∠3°, B = 110∠75° · Power System Analysis I, chapter 6 · asked 2×
- Receiving and sending end powers from ABCD, 132/134 kV · Power System Analysis I, chapter 6
- 110 km, 110 kV line: sending end, regulation, efficiency · Power System Analysis I, chapter 6 · asked 2×
- Sending end active power from ABCD, 132/130.5 kV · Power System Analysis I, chapter 6
- Sending and receiving power, 140∠10° and 132 kV · Power System Analysis I, chapter 6
- Fault at receiving end of 132 kV lines · Power System Analysis II, chapter 3
- Fault at receiving end of 220 kV lines · Power System Analysis II, chapter 3
- Conductor selection, 100 MW 70 km 132 kV · Transmission and Distribution System Design, chapter 4
- Fault at both ends of a 50 Ω line · Power System Analysis II, chapter 3