Power delivered from sending end data, nominal-π
Short answer
Working backward from sending end: receiving voltage V_R = 136.45 kV, current I_R = 223.0 A. Power delivered = 52.08 MW (with 8.04 Mvar supplied by the load side, power factor 0.988 leading).
A 3-phase line is represented by nominal-π model. The series impedance of the line is 12 + j65 Ohms/phase and shunt admittance is j2.5 × 10⁻⁴ S/phase. Compute the power delivered to a load at the receiving end and construct the phasor diagram for the line if the sending end voltage and current are: VS,L = 138.5∠15.2° kV, IS,L = 225∠18.3° A.
Given: , S (so S); kV, A. Working backwards from the sending end through the Π circuit (per phase).
IS IL Z = R + jX IR
o-->--+-----[ R ]--[ jX ]-----+-->--o
| |
VS [Y/2] Ic1 Ic2 [Y/2] VR
| |
o-----+-----------------------+-----o
Step 1: Sending-end phase voltage
Step 2: Sending-end shunt current and series current
Step 3: Receiving-end voltage
Step 4: Receiving-end current
Step 5: Power delivered
So the load receives MW, and the receiving-end p.f. is leading ( leads ); the load side supplies 8.04 Mvar. Sending power is MW, so the line loss is MW.
Phasor diagram ( near reference)
- kV, A (leading by 8.77°).
- is 90° ahead of ; at 15.75°.
- , at 15.2°.
- is 90° ahead of ; at 18.3°.
IC1 ^ IC2 ^
\ | VS (15.2 deg)
\ | / ---+ IL.X
IS,IL \ | / |
^ ^ \ |/ . IL.R |
\ \ \ /.---------+
O---------+-----------> VR (4.5 deg)
IR (13.3 deg) near IL
Answer: Power delivered to the load MW (with 8.04 Mvar supplied by the load side, p.f. 0.988 leading), kV, A.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Nominal-π phasor, sending end, regulation, efficiency · Power System Analysis I, chapter 5
- Sending and receiving power, 140∠10° and 132 kV · Power System Analysis I, chapter 6
- 300 km line: short line vs nominal-π · Power System Analysis I, chapter 5 · asked 2×
- Power output with 46.85 kV sending, 33 kV receiving · Power System Analysis I, chapter 6
- Receiving and sending end powers from ABCD, 132/134 kV · Power System Analysis I, chapter 6
- Model validity and nominal-π ABCD with phasor · Power System Analysis I, chapter 5
- Expression for receiving-end shunt compensation · High Voltage Engineering, chapter 3
- Ybus with nominal π model, line lengths · Power System Analysis II, chapter 1 · asked 2×
- Double-stub shunt tuner for admittance load · RF and Microwave Engineering, chapter 2
- Three-phase connections and series RC phasor · Fundamental of Electrical and Electronics Engineering, chapter 3