- 2070 Bhadra · 2+4+2 marks
Model validity and nominal-π ABCD with phasor
Short answer
The long-line model is exact for any length because it solves distributed-parameter equations; the short-line model neglects shunt capacitance, so it fails for lines >80 km. Nominal-π ABCD: A=D=1+ZY/2, B=Z, C=Y(1+ZY/4). For lagging load, phasor diagram shows V_S built from V_R plus voltage drop across Z, and I_S = I_L + Ic1.
Explain why all lines can be represented by the long transmission line model whereas all the lines cannot be represented by the short transmission line model. Derive expressions of ABCD parameters of a nominal π-model of a medium transmission line. Also draw the phasor diagram for lagging power factor load.
Why the long-line model fits all lines but the short-line model does not
- The long-line model uses distributed parameters and solves the line equations exactly: , , . No approximation is made, so it is valid for any length. For a short line is small, so , , , which is exactly the short-line result.
- The short-line model neglects shunt capacitance (, ). For medium and long lines the charging current is large, so this model gives wrong , , power factor and regulation, and cannot show the Ferranti effect. So it is valid only for short lines (up to about 80 km).
ABCD parameters of the nominal-Π model
Total series impedance in the middle; at each end.
IS IL Z = R + jX IR
o-->--+-----[ R ]--[ jX ]-----+-->--o
| |
VS [Y/2] Ic1 Ic2 [Y/2] VR
| |
o-----+-----------------------+-----o
Phasor diagram (lagging p.f. load, reference)
- lags by ; leads by 90°.
- .
- ( parallel to , 90° ahead of ).
- leads by 90°; .
IC2 ^ + tip of VS
| VS . |
| . | IL.X
| . d |
O---------------------------> VR
\ \ phiR \ IL.R
\ v IL +
v IR IS = IL + IC1 (IC1 is
90 deg ahead of VS)
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Nominal-T phasor diagram and ABCD parameters · Power System Analysis I, chapter 5 · asked 2×
- Nominal-π derivation, losses and UPF phasor diagram · Power System Analysis I, chapter 5
- Classification of lines by length and model validity · Power System Analysis I, chapter 5
- Nominal-π model ABCD derivation · Power System Analysis I, chapter 5
- ABCD constants by nominal-T model · Power System Analysis I, chapter 5
- Nominal-T derivation, phasor, losses, regulation · Power System Analysis I, chapter 5
- Ybus with nominal π model, line lengths · Power System Analysis II, chapter 1 · asked 2×
- Loaded transformer and phasor diagram for inductive load · Electrical Machines I, chapter 2
- Derive input impedance of transmission line · Electromagnetism, chapter 5
- Reactive power and power phasor diagram · Basic Electrical Engineering, chapter 7