Nominal-π derivation, losses and UPF phasor diagram
Short answer
For a 200 km line (medium), nominal-π ABCD: A=D=1+ZY/2, B=Z, C=Y(1+ZY/4). Active loss P_loss=3|I_L|²R, reactive loss Q_loss=3|I_L|²X−3(ωC/2)(|V_S|²+|V_R|²). Phasor diagram for unity pf: V_R reference, I_R in phase; I_C2 leads V_R 90°; I_L=I_R+I_C2; V_S=V_R+I_LR+jI_LX; I_C1 leads V_S90°; I_S=I_L+I_C1.
For a 3-ph, 200 km long transmission line, derive an expression relating sending end voltage and current to receiving end voltage and current using the nominal-π model. Also write down the expressions for determining active and reactive power losses in the line. Construct a phasor diagram of currents and voltages for a unity power factor load at the receiving end.
A 200 km line is a medium line, so its shunt capacitance cannot be ignored. In the nominal-Π model the total series impedance is lumped in the middle and is placed at each end (all quantities per phase).
IS IL Z = R + jX IR
o-->--+-----[ R ]--[ jX ]-----+-->--o
| |
VS [Y/2] Ic1 Ic2 [Y/2] VR
| |
o-----+-----------------------+-----o
Relation between sending and receiving quantities
Current through the receiving-end shunt:
Series current:
In matrix form:
Active and reactive power losses (3-phase)
With at each end:
The first term of is the reactive power absorbed by the series inductance. The second is the reactive power generated by the two shunt capacitances. A negative means the line supplies net reactive power, which is normal at light load.
Phasor diagram for unity p.f. load
Take as reference; is in phase with .
- leads by 90°.
- leads slightly.
- : is parallel to , is perpendicular to .
- leads by 90°; .
IS
IC1 ^ ^ VS
\ | IL / |
\ | / / | IL.X
IC2 ^ \|/ / |
| / d /____|
|/ / IL.R
O------------------------> VR , IR
At unity p.f. the drop is almost at right angles to , so is only slightly greater than while the load angle is noticeable. leads because of the two charging currents.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Long line sending end voltage derivation · Power System Analysis I, chapter 5
- Nominal-T derivation, phasor, losses, regulation · Power System Analysis I, chapter 5
- Nominal-π phasor, sending end, regulation, efficiency · Power System Analysis I, chapter 5
- 280 km, 60 Hz line: nominal-π vs long line · Power System Analysis I, chapter 5 · asked 2×
- Power delivered from sending end data, nominal-π · Power System Analysis I, chapter 5
- 110 km, 110 kV line: sending end, regulation, efficiency · Power System Analysis I, chapter 6 · asked 2×
- Receiving-end voltage infinite at 1500 km · High Voltage Engineering, chapter 3
- Expression for receiving-end shunt compensation · High Voltage Engineering, chapter 3
- Ybus with nominal π model, line lengths · Power System Analysis II, chapter 1 · asked 2×
- Fault level at end of two 200 km lines · Power System Analysis II, chapter 3 · asked 2×