Nominal-π derivation, losses and UPF phasor diagram

Short answer

For a 200 km line (medium), nominal-π ABCD: A=D=1+ZY/2, B=Z, C=Y(1+ZY/4). Active loss P_loss=3|I_L|²R, reactive loss Q_loss=3|I_L|²X−3(ωC/2)(|V_S|²+|V_R|²). Phasor diagram for unity pf: V_R reference, I_R in phase; I_C2 leads V_R 90°; I_L=I_R+I_C2; V_S=V_R+I_LR+jI_LX; I_C1 leads V_S90°; I_S=I_L+I_C1.

For a 3-ph, 200 km long transmission line, derive an expression relating sending end voltage and current to receiving end voltage and current using the nominal-π model. Also write down the expressions for determining active and reactive power losses in the line. Construct a phasor diagram of currents and voltages for a unity power factor load at the receiving end.

A 200 km line is a medium line, so its shunt capacitance cannot be ignored. In the nominal-Π model the total series impedance Z=R+jXZ = R + jX is lumped in the middle and Y/2Y/2 is placed at each end (all quantities per phase).

 IS       IL    Z = R + jX        IR
 o-->--+-----[ R ]--[ jX ]-----+-->--o
       |                       |
 VS  [Y/2] Ic1           Ic2 [Y/2]  VR
       |                       |
 o-----+-----------------------+-----o

Relation between sending and receiving quantities

Current through the receiving-end shunt: IC2=Y2VRI_{C2} = \frac{Y}{2}V_R

Series current: IL=IR+Y2VRI_L = I_R + \frac{Y}{2}V_R

VS=VR+ZIL=(1+ZY2)VR+ZIRIS=IL+Y2VS=Y(1+ZY4)VR+(1+ZY2)IR\begin{aligned} V_S &= V_R + ZI_L = \left(1 + \frac{ZY}{2}\right)V_R + ZI_R \\ I_S &= I_L + \frac{Y}{2}V_S = Y\left(1 + \frac{ZY}{4}\right)V_R + \left(1 + \frac{ZY}{2}\right)I_R \end{aligned}

In matrix form:

[VSIS]=[1+ZY2ZY(1+ZY4)1+ZY2][VRIR]\begin{bmatrix} V_S \\ I_S \end{bmatrix} = \begin{bmatrix} 1 + \frac{ZY}{2} & Z \\ Y\left(1 + \frac{ZY}{4}\right) & 1 + \frac{ZY}{2} \end{bmatrix}\begin{bmatrix} V_R \\ I_R \end{bmatrix}

Active and reactive power losses (3-phase)

With Y/2=jωC/2Y/2 = j\omega C/2 at each end:

Ploss=3∣IL∣2R=PS−PRQloss=3∣IL∣2X−3ωC2(∣VS∣2+∣VR∣2)=QS−QR\begin{aligned} P_{loss} &= 3|I_L|^2 R = P_S - P_R \\ Q_{loss} &= 3|I_L|^2X - 3\frac{\omega C}{2}\left(|V_S|^2 + |V_R|^2\right) = Q_S - Q_R \end{aligned}

The first term of QlossQ_{loss} is the reactive power absorbed by the series inductance. The second is the reactive power generated by the two shunt capacitances. A negative QlossQ_{loss} means the line supplies net reactive power, which is normal at light load.

Phasor diagram for unity p.f. load

Take VRV_R as reference; IRI_R is in phase with VRV_R.

  1. IC2I_{C2} leads VRV_R by 90°.
  2. IL=IR+IC2I_L = I_R + I_{C2} leads VRV_R slightly.
  3. VS=VR+ILR+jILXV_S = V_R + I_LR + jI_LX: ILRI_LR is parallel to ILI_L, ILXI_LX is perpendicular to ILI_L.
  4. IC1I_{C1} leads VSV_S by 90°; IS=IL+IC1I_S = I_L + I_{C1}.
                  IS
         IC1 ^   ^         VS
              \  |  IL   / |
               \ | /    /  | IL.X
          IC2 ^ \|/    /   |
              | /   d /____|
              |/    /  IL.R
   O------------------------> VR , IR

At unity p.f. the ILXI_LX drop is almost at right angles to VRV_R, so ∣VS∣|V_S| is only slightly greater than ∣VR∣|V_R| while the load angle δ\delta is noticeable. ISI_S leads IRI_R because of the two charging currents.