Nominal-T derivation, phasor, losses, regulation

Short answer

Nominal-T: half series impedance Z/2 in each arm, shunt Y at centre. VS = (1+ZY/2)VR + Z(1+ZY/4)IR, IS = Y VR + (1+ZY/2)IR. Power loss Ploss = 3(|IR|²+|IS|²)R/2. Regulation uses no-load VR = |VS|/|A|. Efficiency = PR/(PR+Ploss). Phasor diagram builds VC then IS and VS.

Starting from a suitable point, derive expressions relating sending end voltage and current for a medium length transmission line using the nominal-T model. Also construct the phasor diagram and expressions to compute power loss in the line, voltage regulation and efficiency.

In the nominal-T model of a medium line, the total shunt admittance Y=jωCY = j\omega C is placed at the middle of the line, and half the series impedance (Z/2Z/2) is placed in each arm. Values are per phase.

 IS     Z/2            Z/2     IR
 o-->--[R/2 jX/2]--+--[R/2 jX/2]-->--o
                   |
 VS              [ Y ] Ic   (VC)     VR
                   |
 o-----------------+-----------------o

Sending-end voltage and current

Step 1: Voltage across the shunt (mid-point):

VC=VR+Z2IRV_C = V_R + \frac{Z}{2}I_R

Step 2: Shunt current and sending current:

IC=YVC=YVR+ZY2IRIS=IR+IC=YVR+(1+ZY2)IR\begin{aligned} I_C &= YV_C = YV_R + \frac{ZY}{2}I_R \\ I_S &= I_R + I_C = YV_R + \left(1 + \frac{ZY}{2}\right)I_R \end{aligned}

Step 3: Sending-end voltage:

VS=VC+Z2IS=VR+Z2IR+Z2[YVR+(1+ZY2)IR]VS=(1+ZY2)VR+Z(1+ZY4)IR\begin{aligned} V_S &= V_C + \frac{Z}{2}I_S = V_R + \frac{Z}{2}I_R + \frac{Z}{2}\left[YV_R + \left(1 + \frac{ZY}{2}\right)I_R\right] \\ V_S &= \left(1 + \frac{ZY}{2}\right)V_R + Z\left(1 + \frac{ZY}{4}\right)I_R \end{aligned}

So A=D=1+ZY2A = D = 1 + \frac{ZY}{2}, B=Z(1+ZY4)B = Z\left(1 + \frac{ZY}{4}\right), C=YC = Y.

Phasor diagram (lagging load, VRV_R reference)

  1. IRI_R lags VRV_R by ϕR\phi_R.
  2. VC=VR+IRR2+jIRX2V_C = V_R + I_R\frac{R}{2} + jI_R\frac{X}{2}.
  3. ICI_C leads VCV_C by 90°; IS=IR+ICI_S = I_R + I_C.
  4. VS=VC+ISR2+jISX2V_S = V_C + I_S\frac{R}{2} + jI_S\frac{X}{2}.
                 IC ^          /| VS
                    |   VC   / IS.X/2
                    |   /|  /
                    |  / |IR.X/2
                    | /  /IR.R/2
   O-----------------------> VR
     \  \ phiR
      \   v IS  (IS = IR + IC)
       v
       IR

Power loss

Ploss=3(∣IR∣2+∣IS∣2)R2Qloss=3(∣IR∣2+∣IS∣2)X2−3∣VC∣2ωC\begin{aligned} P_{loss} &= 3\left(|I_R|^2 + |I_S|^2\right)\frac{R}{2} \\ Q_{loss} &= 3\left(|I_R|^2 + |I_S|^2\right)\frac{X}{2} - 3|V_C|^2\omega C \end{aligned}

Voltage regulation

No-load receiving voltage =∣VS∣/∣A∣= |V_S|/|A|:

%VR=∣VS∣/∣A∣−∣VR∣∣VR∣×100,∣A∣=∣1+ZY2∣\%\text{VR} = \frac{|V_S|/|A| - |V_R|}{|V_R|}\times100, \quad |A| = \left|1 + \frac{ZY}{2}\right|

Efficiency

η=PRPR+Ploss×100=3∣VR∣∣IR∣cos⁡ϕR3∣VR∣∣IR∣cos⁡ϕR+3(∣IR∣2+∣IS∣2)R2×100\eta = \frac{P_R}{P_R + P_{loss}}\times100 = \frac{3|V_R||I_R|\cos\phi_R}{3|V_R||I_R|\cos\phi_R + 3\left(|I_R|^2 + |I_S|^2\right)\frac{R}{2}}\times100