Nominal-T derivation, phasor, losses, regulation
Short answer
Nominal-T: half series impedance Z/2 in each arm, shunt Y at centre. VS = (1+ZY/2)VR + Z(1+ZY/4)IR, IS = Y VR + (1+ZY/2)IR. Power loss Ploss = 3(|IR|²+|IS|²)R/2. Regulation uses no-load VR = |VS|/|A|. Efficiency = PR/(PR+Ploss). Phasor diagram builds VC then IS and VS.
Starting from a suitable point, derive expressions relating sending end voltage and current for a medium length transmission line using the nominal-T model. Also construct the phasor diagram and expressions to compute power loss in the line, voltage regulation and efficiency.
In the nominal-T model of a medium line, the total shunt admittance is placed at the middle of the line, and half the series impedance () is placed in each arm. Values are per phase.
IS Z/2 Z/2 IR
o-->--[R/2 jX/2]--+--[R/2 jX/2]-->--o
|
VS [ Y ] Ic (VC) VR
|
o-----------------+-----------------o
Sending-end voltage and current
Step 1: Voltage across the shunt (mid-point):
Step 2: Shunt current and sending current:
Step 3: Sending-end voltage:
So , , .
Phasor diagram (lagging load, reference)
- lags by .
- .
- leads by 90°; .
- .
IC ^ /| VS
| VC / IS.X/2
| /| /
| / |IR.X/2
| / /IR.R/2
O-----------------------> VR
\ \ phiR
\ v IS (IS = IR + IC)
v
IR
Power loss
Voltage regulation
No-load receiving voltage :
Efficiency
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Nominal-π derivation, losses and UPF phasor diagram · Power System Analysis I, chapter 5
- Nominal-π phasor, sending end, regulation, efficiency · Power System Analysis I, chapter 5
- Long line sending end voltage derivation · Power System Analysis I, chapter 5
- Power delivered from sending end data, nominal-π · Power System Analysis I, chapter 5
- Nominal-T relations, losses and Ferranti condition · Power System Analysis I, chapter 5
- Model validity and nominal-π ABCD with phasor · Power System Analysis I, chapter 5
- Power loss change on doubling line length · Transmission and Distribution System Design, chapter 7
- Ybus with nominal π model, line lengths · Power System Analysis II, chapter 1 · asked 2×