- 2068 Bhadra · 8 marks
Nominal-T relations, losses and Ferranti condition
Short answer
In the nominal-T model, A = D = 1 + ZY/2, B = Z(1 + ZY/4), C = Y. Active loss = 3(|I_S|² + |I_R|²)R/2, reactive loss includes line inductive and capacitive parts. Ferranti effect occurs at light load when |1 + ZY/2| < 1, making receiving voltage exceed sending voltage due to capacitance.
Derive the expressions relating sending end current and voltage to the receiving end voltage and current in a medium length transmission line by nominal-T model. Express the active and reactive losses in the line and the condition for voltage at the receiving end being higher than at the sending end.
In the nominal-T model, the total shunt admittance is at the middle of the line and is in each arm (per phase).
IS Z/2 Z/2 IR
o-->--[R/2 jX/2]--+--[R/2 jX/2]-->--o
|
VS [ Y ] Ic (VC) VR
|
o-----------------+-----------------o
Sending-end voltage and current
So , , .
Active and reactive losses (3-phase)
Current flows in the sending half and in the receiving half:
The last term is the reactive power generated by the line capacitance. Equivalently, and .
Condition for receiving voltage higher than sending voltage
At no load or light load ():
With and :
Neglecting the small term, when
which is always true for a practical line (and small). So at light load the receiving voltage rises above the sending voltage; this is the Ferranti effect. The rise is
so it grows with the square of line length. With load, happens when the capacitive charging current outweighs the drop of the load current, i.e. when the load is below about SIL or is leading.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Nominal-π derivation, losses and UPF phasor diagram · Power System Analysis I, chapter 5
- Nominal-π phasor, sending end, regulation, efficiency · Power System Analysis I, chapter 5
- Long line sending end voltage derivation · Power System Analysis I, chapter 5
- Receiving and sending end powers from ABCD, 132/134 kV · Power System Analysis I, chapter 6
- Nominal-T derivation, phasor, losses, regulation · Power System Analysis I, chapter 5
- Power delivered from sending end data, nominal-π · Power System Analysis I, chapter 5
- Receiving-end voltage infinite at 1500 km · High Voltage Engineering, chapter 3
- T/F: more circuits rather than higher voltage · Transmission and Distribution System Design, chapter 2
- Expression for receiving-end shunt compensation · High Voltage Engineering, chapter 3
- Ybus with nominal π model, line lengths · Power System Analysis II, chapter 1 · asked 2×