Power loss change on doubling line length
Short answer
Doubling length with same load density doubles total load and resistance. Power loss becomes (2I)² × (2rl) = 8 times the original, so loss increases 8-fold (∝l³). Supplied load only doubles, so percentage loss quadruples.
For same load density of the load centre and same conductor what will be the change in power loss by doubling the length of the line?
With the same load density (kW per km) and the same conductor, doubling the length of a uniformly loaded line doubles both its total load and its resistance.
Original line (length , uniform load density kW/km, sending-end current , resistance ):
(for a uniformly distributed load the loss is one-third of the end-loaded value).
Doubled line (length ): total load , so current ; resistance :
Result:
- Power loss increases 8 times ().
- The load supplied only doubles, so the percentage power loss increases 4 times ().
- Similarly, voltage drop () increases 4 times.
This is why LT feeders must be kept short; in a large area it is better to use more transformers placed near load centres than to extend long LT lines.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- T/F: % power loss affected by load factor · Transmission and Distribution System Design, chapter 6
- T/F: power transfer capability vs line length · Transmission and Distribution System Design, chapter 2 · asked 2×
- Conductor selection, 220 kV line for 200 MW · Transmission and Distribution System Design, chapter 4
- T/F: % power loss equals % energy loss · Transmission and Distribution System Design, chapter 6
- Loss and voltage drop, 16 km uniformly varying load · Transmission and Distribution System Design, chapter 7
- Selecting load centre and transformer, rural/urban · Transmission and Distribution System Design, chapter 7 · asked 3×
- Line power loss, 138.5∠8° kV and 132 kV · Power System Analysis I, chapter 6
- Charging reactive power of line at no load · High Voltage Engineering, chapter 3 · asked 2×
- Line with 50+j50 load, first maximum, power · Electromagnetism, chapter 5
- Open flat belt power and cross belt length · Machine Design I, chapter 8
All Transmission and Distribution System Design chapter 7 questions →