Power loss change on doubling line length

Short answer

Doubling length with same load density doubles total load and resistance. Power loss becomes (2I)² × (2rl) = 8 times the original, so loss increases 8-fold (∝l³). Supplied load only doubles, so percentage loss quadruples.

For same load density of the load centre and same conductor what will be the change in power loss by doubling the length of the line?

With the same load density (kW per km) and the same conductor, doubling the length of a uniformly loaded line doubles both its total load and its resistance.

Original line (length ll, uniform load density λ\lambda kW/km, sending-end current I∝λlI \propto \lambda l, resistance R=rlR = rl):

Ploss,1=3×I2R3=I2rlP_{loss,1} = 3 \times \frac{I^2 R}{3} = I^2 r l

(for a uniformly distributed load the loss is one-third of the end-loaded value).

Doubled line (length 2l2l): total load =2λl= 2\lambda l, so current I2=2II_2 = 2I; resistance R2=2rlR_2 = 2rl:

Ploss,2=(2I)2×r(2l)=8I2rlPloss,2Ploss,1=8\begin{aligned} P_{loss,2} &= (2I)^2 \times r(2l) = 8 I^2 r l \\ \frac{P_{loss,2}}{P_{loss,1}} &= 8 \end{aligned}

Result:

  • Power loss increases 8 times (∝l3\propto l^3).
  • The load supplied only doubles, so the percentage power loss increases 4 times (∝l2\propto l^2).
  • Similarly, voltage drop (∝I×l\propto I \times l) increases 4 times.

This is why LT feeders must be kept short; in a large area it is better to use more transformers placed near load centres than to extend long LT lines.