Loaded transformer and phasor diagram for inductive load

Short answer

When loaded, secondary MMF opposes main flux, so primary draws an extra current I2' to cancel it, keeping core flux nearly constant. The primary current is I0 + I2'. For an inductive load, I2 lags V2, V2 is less than E2 due to impedance drops, and I1 lags V1.

Explain the loaded operation of transformer. Draw the phasor diagram of a power transformer for inductive load.

Loaded operation of a transformer

When a load is connected to the secondary, a current I2I_2 flows, set by the load: I2=V2/ZLI_2 = V_2/Z_L.

  1. I2I_2 in N2N_2 turns produces an MMF N2I2N_2I_2 that, by Lenz's law, opposes the main flux ϕ\phi.
  2. The flux tends to fall, so the back EMF E1E_1 falls slightly and the primary draws an extra current I2′I_2' from the supply.
  3. I2′I_2' is just large enough for its MMF to cancel the secondary MMF: N1I2′=N2I2N_1I_2' = N_2I_2, so I2′=KI2I_2' = KI_2 (with K=N2/N1K = N_2/N_1).
  4. The total primary current is the phasor sum Iˉ1=Iˉ0+Iˉ2′\bar I_1 = \bar I_0 + \bar I_2'.
  5. Because the net MMF is still N1I0N_1I_0, the core flux stays almost constant from no load to full load, so the iron loss is constant.

In a real transformer the windings have resistance and leakage reactance, so:

Vˉ1=−Eˉ1+Iˉ1(R1+jX1)Vˉ2=Eˉ2−Iˉ2(R2+jX2)\begin{aligned} \bar V_1 &= -\bar E_1 + \bar I_1(R_1 + jX_1) \\ \bar V_2 &= \bar E_2 - \bar I_2(R_2 + jX_2) \end{aligned}

As the load increases, these drops increase, so V2V_2 falls (voltage regulation).

Phasor diagram for inductive (lagging) load

Steps: draw ϕ\phi as the reference; E1E_1 and E2E_2 lag ϕ\phi by 90°; I0I_0 leads ϕ\phi by a small angle (because of core loss); I2I_2 lags V2V_2 by ϕ2\phi_2; V2=E2−I2R2−jI2X2V_2 = E_2 - I_2R_2 - jI_2X_2; I2′I_2' is drawn equal and opposite to I2I_2; I1=I0+I2′I_1 = I_0 + I_2'; V1=−E1+I1R1+jI1X1V_1 = -E_1 + I_1R_1 + jI_1X_1.

                   V1
                   ^
                  /|  I1.X1 (perpendicular to I1)
                 / |
       -E1 ^    /--+  I1.R1 (parallel to I1)
           |   /
           |  /         ^ I2' (equal and opposite to I2)
           | /        /
           |/       /   ^ I1 = I0 + I2'
           |      /   /
           |    /   /
           |  /   /  ___...---> I0 (leads phi slightly)
           |/  /..--'
  ---------O-------------------------> phi (main flux, reference)
          /|
         / |
        /  |
       v   |
     I2    v V2 = E2 - I2(R2 + jX2)
 (lags V2  |
  by phi2) v E2   (E1 also lies along this line)

  phi1 = angle between V1 and I1; phi2 = angle between V2 and I2

(For clarity many textbooks take K=1K = 1, so E1=E2E_1 = E_2 and I2′=I2I_2' = I_2 in magnitude.)

Key features for an inductive load:

  • I2I_2 lags V2V_2 by ϕ2\phi_2, so it points down and to the left of V2V_2; I2′I_2' is exactly opposite to it, lagging −E1-E_1.
  • I1I_1 lags V1V_1 by ϕ1\phi_1, with ϕ1\phi_1 slightly greater than ϕ2\phi_2 because of I0I_0 and the drops.
  • V2<E2V_2 < E_2 and V1>E1V_1 > E_1; the drop is largest for lagging loads.
  • On full load I0I_0 is small compared with I2′I_2', so I1≈I2′I_1 \approx I_2' and I1I2≈K\frac{I_1}{I_2} \approx K.