- 2071 Bhadra · 4+3 marks
Loaded transformer and phasor diagram for inductive load
Short answer
When loaded, secondary MMF opposes main flux, so primary draws an extra current I2' to cancel it, keeping core flux nearly constant. The primary current is I0 + I2'. For an inductive load, I2 lags V2, V2 is less than E2 due to impedance drops, and I1 lags V1.
Explain the loaded operation of transformer. Draw the phasor diagram of a power transformer for inductive load.
Loaded operation of a transformer
When a load is connected to the secondary, a current flows, set by the load: .
- in turns produces an MMF that, by Lenz's law, opposes the main flux .
- The flux tends to fall, so the back EMF falls slightly and the primary draws an extra current from the supply.
- is just large enough for its MMF to cancel the secondary MMF: , so (with ).
- The total primary current is the phasor sum .
- Because the net MMF is still , the core flux stays almost constant from no load to full load, so the iron loss is constant.
In a real transformer the windings have resistance and leakage reactance, so:
As the load increases, these drops increase, so falls (voltage regulation).
Phasor diagram for inductive (lagging) load
Steps: draw as the reference; and lag by 90°; leads by a small angle (because of core loss); lags by ; ; is drawn equal and opposite to ; ; .
V1
^
/| I1.X1 (perpendicular to I1)
/ |
-E1 ^ /--+ I1.R1 (parallel to I1)
| /
| / ^ I2' (equal and opposite to I2)
| / /
|/ / ^ I1 = I0 + I2'
| / /
| / /
| / / ___...---> I0 (leads phi slightly)
|/ /..--'
---------O-------------------------> phi (main flux, reference)
/|
/ |
/ |
v |
I2 v V2 = E2 - I2(R2 + jX2)
(lags V2 |
by phi2) v E2 (E1 also lies along this line)
phi1 = angle between V1 and I1; phi2 = angle between V2 and I2
(For clarity many textbooks take , so and in magnitude.)
Key features for an inductive load:
- lags by , so it points down and to the left of ; is exactly opposite to it, lagging .
- lags by , with slightly greater than because of and the drops.
- and ; the drop is largest for lagging loads.
- On full load is small compared with , so and .
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Transformer no-load and load operation, constant core flux · Electrical Machines I, chapter 2 · asked 5×
- Real transformer no-load operation and amp-turn balance · Electrical Machines I, chapter 2
- Transformer no-load operation and ideal transformer properties · Electrical Machines I, chapter 2
- Full-load efficiency of 500 kVA transformer · Electrical Machines I, chapter 2
- Full-load and half-load efficiency of 100 kVA transformer · Electrical Machines I, chapter 2
- Efficiency of 5 kVA transformer at 2 kW load · Electrical Machines I, chapter 2
- Practical vs ideal transformer, phasor diagram · Electrical Machines, chapter 2
- No-load and loaded operation, constant flux · Electrical Machines, chapter 2 · asked 3×
- Transformer on load, phasor diagrams · Electrical Machine, chapter 2
- Transformer on load and no load, phasor diagrams · Electrical Machines, chapter 2