- 2078 Poush · 2+6 marks
Practical vs ideal transformer, phasor diagram
Short answer
An ideal transformer has no resistance, no leakage, no core loss, and zero no-load current. A practical transformer has winding resistances, leakage reactances, core loss, and draws an exciting current I0. On load, V2 = E2 – I2(R2 + jX2) and I1 = I0 + I2/a, where a = N1/N2.
How practical transformer is different from ideal one? Explain with phasor diagram the operation of practical transformer when secondary is connected to load.
Practical vs ideal transformer
| Point | Ideal transformer | Practical transformer |
|---|---|---|
| Winding resistance | Zero | , present (copper loss) |
| Leakage flux | None (unity coupling) | Leakage reactances , |
| Core permeability | Infinite | Finite, needs magnetising current |
| Core loss | Zero | Hysteresis and eddy loss, current |
| No-load current | Zero | Small |
| Efficiency | 100% | 95 to 99% |
| Voltage regulation | Zero | Non-zero |
| Exactly | Slightly different on load |
Operation of a practical transformer on load
When load current flows, the secondary terminal voltage and primary current are given by
Phasor diagram (inductive load, lagging ):
V1 (applied)
/|
I1X1/ | Steps:
/ | I1R1 1. Take flux phi as reference.
-E1 /___| 2. E1, E2 lag phi by 90 deg.
| 3. I2 lags V2 by phi2.
| E2 4. E2 = V2 + I2R2 + jI2X2.
| \ I2X2 5. I1' = I2/a opposes the I2 mmf.
phi | \ I2R2 6. I1 = I0 + I1'.
v \V2 7. V1 = -E1 + I1R1 + jI1X1.
Steps in words:
- Draw the flux as reference. The emfs and lag it by 90°, and is drawn opposite to .
- Draw , then lagging it by . Add (parallel to ) and (90° ahead) to reach .
- The load component is drawn opposite to (scaled by ). The no-load current is drawn leading the flux by the hysteresis angle, with along and along .
- . Add and to to get .
The angle between and is the primary power factor angle , slightly different from because of and the drops.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Loaded transformer and phasor diagram for inductive load · Electrical Machines I, chapter 2
- Transformer no-load operation and ideal transformer properties · Electrical Machines I, chapter 2
- Transformer on load and no load, phasor diagrams · Electrical Machines, chapter 2
- Transformer no-load and load operation, constant core flux · Electrical Machines I, chapter 2 · asked 5×
- Ideal transformer no-load and loaded, ratios · Electrical Machines, chapter 2 · asked 2×
- Real transformer no-load operation and amp-turn balance · Electrical Machines I, chapter 2
- Transformer on load, phasor diagrams · Electrical Machine, chapter 2
- Ideal vs practical filters and scaling · Filter Design, chapter 1 · asked 2×
- Filter importance in communication; ideal vs practical · Filter Design, chapter 1 · asked 2×
- Ideal transformer no-load, load, ratios · Electrical Machine, chapter 2 · asked 2×