- 2068 Magh · 8 marks
Transformer on load and no load, phasor diagrams
Short answer
At no load, primary draws a small lagging exciting current I0 with core-loss and magnetizing components. On resistive load, I2 is in phase with V2, and E2 > V2 giving a slight voltage drop. On capacitive load, I2 leads V2; the reactance drop partially opposes V2, so E2 may be smaller than V2, causing a voltage rise (negative regulation).
Explain the transformer on load and no load with the phasor diagram of resistive and capacitive load.
A practical transformer has winding resistances , leakage reactances and a core that draws an exciting current .
No-load operation
The secondary is open (). The primary draws only , which has two components:
V1 (= -E1 approx)
^
|
Ic | . I0
(along V1)| .
| . phi0 = angle between V1 and I0
|. (about 75-80 deg)
+-------------------> Im, flux phi
|
v
E1, E2 (lag phi by 90 deg)
- is in phase with and supplies the core loss.
- lags by 90°, and the flux is in phase with .
- and lag by 90°, so is opposite to .
- is small (2 to 5% of full-load current) and lags by , so the no-load power factor is low (about 0.1 to 0.25).
On load
The secondary current flows, and the primary takes the additional load component , so (phasor sum). The voltage equations are
Resistive load. is in phase with . is found by adding to the drop (in phase with ) and (90° ahead of ). So and the terminal voltage falls on load. is in phase with (it is drawn in phase with ), and is close to . The primary power factor is nearly unity.
Resistive load (phasors referred to secondary)
E2
/|
/ | I2X2
/ |
/___|______
V2 I2R2 I2 along V2
Capacitive load. leads by . The drops and are drawn along and 90° ahead of it. Because is now ahead of , the drop points partly opposite to , and becomes smaller than : approximately . So the secondary terminal voltage rises on load (negative regulation) when the leading power factor is low enough.
Capacitive load (V2 as reference, I2 leads V2 by phi2)
E2 tip <-----------+
.' I2X2 /
.' / I2R2 (along I2)
O ----------------------------+ V2
E2 runs from O to E2 tip and is shorter than V2
In each case, is obtained as , and completes the primary diagram. For the capacitive load leads , so the primary power factor is leading when the load current is large compared with .
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Transformer at resistive, inductive, capacitive loads · Electrical Machines, chapter 2
- Loaded transformer and phasor diagram for inductive load · Electrical Machines I, chapter 2
- Practical vs ideal transformer, phasor diagram · Electrical Machines, chapter 2
- Transformer no-load and load operation, constant core flux · Electrical Machines I, chapter 2 · asked 5×
- Ideal transformer no-load and loaded, ratios · Electrical Machines, chapter 2 · asked 2×
- Transformer no-load operation and ideal transformer properties · Electrical Machines I, chapter 2
- Transformer on load, phasor diagrams · Electrical Machine, chapter 2
- Ideal transformer no-load, load, ratios · Electrical Machine, chapter 2 · asked 2×
- No load current of single phase transformer · Electric Machine Design, chapter 3
- Why terminal voltage exceeds emf on capacitive load · Electric Machines II, chapter 1 · asked 3×