- 2071 Magh (old course) · 8 marks
Transformer at resistive, inductive, capacitive loads
Short answer
With resistive load, I2 is in phase with V2: E2 = V2 + I2R02 (small drop). Inductive load: I2 lags V2; E2 = V2 + I2(R02 cosφ + X02 sinφ) yields a larger drop and poorer regulation. Capacitive load: I2 leads V2; the reactive drop subtracts, making E2 possibly less than V2 and giving a voltage rise.
Explain the operation of transformer at different loading conditions (resistive, inductive, capacitive) showing their corresponding circuit diagram and phasor diagram.
The transformer is treated as a practical one with winding resistances and leakage reactances . For any load, with the turns ratio :
Circuit diagram
I1 R1 X1 R2 X2 I2
o--/\/\--UUU--+ +--/\/\--UUU--o
| | |
V1 E1 ( ) ( ) E2 Z (load)
| | |
o-------------+--+-------------o
ideal transformer N1:N2
Phasor diagrams (drawn with as the reference)
For each load, add to the drop (parallel to ) and then (90° ahead of ) to obtain .
| Load | w.r.t. | Resulting | Effect on secondary voltage |
|---|---|---|---|
| Resistive () | In phase | slightly | Small fall |
| Inductive (lagging) | Lags by | much larger than | Largest fall |
| Capacitive (leading) | Leads by | may be smaller than | Rise (negative regulation) |
Inductive Resistive Capacitive
(I2 lags V2) (I2 = V2) (I2 leads V2)
E2 (big) E2 I2 /
/| /| /
/ | I2X2 / | I2X2 E2 /__ V2 (> E2)
/__| /__|
V2 I2R2 V2 I2R2
(I2 below V2) (I2 along V2)
Primary side: in each case, the load component has the same phase angle relative to as has relative to . It is added to the no-load current (which lags by about 78°) to give . Then is the phasor sum of , and .
Result: the inductive load gives the poorest regulation, the resistive load an intermediate value, and a capacitive load can give a voltage rise. The primary power factor follows the load: lagging for an inductive load, nearly unity for a resistive load, and leading for a strongly capacitive load.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Loaded transformer and phasor diagram for inductive load · Electrical Machines I, chapter 2
- Practical vs ideal transformer, phasor diagram · Electrical Machines, chapter 2
- Transformer on load and no load, phasor diagrams · Electrical Machines, chapter 2
- Need and conditions for parallel operation of transformers · Electrical Machines I, chapter 2
- Conditions for parallel operation of transformers · Electrical Machines I, chapter 2
- Conditions for parallel operation of transformers · Electrical Machines, chapter 2
- MCB types for resistive and inductive loads · Switchgear and Protection, chapter 3
- Transformer on load, phasor diagrams · Electrical Machine, chapter 2
- Inductive noise and capacitive coupling shielding · Instrumentation II, chapter 6
- Grounding and shielding; inductive and capacitive shielding · Instrumentation II, chapter 6