Power output with 46.85 kV sending, 33 kV receiving
Short answer
Power output is about 20.95 MW at 0.8 pf lagging. Sending end power factor is approximately 0.648 lagging, computed from voltage drop across series impedance (20.62∠75.96° Ω).
The sending end voltage of a three phase overhead line with a series impedance of (20.62∠75.96°) ohm is 46.85 kV while the receiving end is 33 kV. Determine the power output at 0.8 pf lagging and the sending end power factor.
Short line with per phase.
Method
Take (line, kV) as reference. For three-phase in MW/MVAr at the receiving end:
Multiplying by and taking magnitudes:
Substitution
At 0.8 pf lagging, . With , , , :
Expanding:
Taking the positive root:
Check: kV.
Sending-end power factor
(Check: MVA, and MVA.)
Answer: Power output ≈ 20.95 MW at 0.8 pf lag; sending-end pf ≈ 0.648 lagging.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- 8 km line receiving 15000 kVA at 33 kV · Power System Analysis I, chapter 6
- Receiving and sending end powers from ABCD, 132/134 kV · Power System Analysis I, chapter 6
- 110 km, 110 kV line: sending end, regulation, efficiency · Power System Analysis I, chapter 6 · asked 2×
- Sending and receiving power, 140∠10° and 132 kV · Power System Analysis I, chapter 6
- Sending end from A = 0.98∠3°, B = 110∠75° · Power System Analysis I, chapter 6 · asked 2×
- Static compensation to hold sending end at 140 kV · Power System Analysis I, chapter 6
- Fault at far end of 33 kV line · Power System Analysis II, chapter 3
- Fault at load end of overhead line · Power System Analysis II, chapter 3
- Fault at receiving end of 220 kV lines · Power System Analysis II, chapter 3
- Fault at receiving end of 132 kV lines · Power System Analysis II, chapter 3