Fault cleared at 45°: stability and maximum swing
Short answer
Initial power is 0.821 pu. During the three-phase fault at bus 1, electrical power is zero; clearing at 45° leaves the decelerating area larger than the accelerating area, so the system is stable and the maximum rotor swing is about 63.4°.
The power system shown below is operating initially at power angle δ = 20°. Calculate the power delivered to the infinite bus at normal operation. If a 3-phase to ground fault occurs at bus (1) and fault is cleared when the power angle δ reaches 45°, determine whether system come back to stable or not? If yes, calculate the maximum δ-swing angle. [Figure: generator E = 1.2 pu∠δ, j0.25 pu to bus (1); two parallel lines each j0.5 pu (breakers at both ends) from bus (1) to bus (2), the infinite bus V = 1 pu∠0°]
Data: pu, pu, , two lines of pu each, .
Assumption: the bus fault is temporary, so after clearing both lines are in service and the post-fault curve equals the pre-fault curve.
Step 1: Normal operation
Power delivered at normal operation: 0.821 pu.
Step 2: During the fault
A 3-phase fault at bus (1) puts the line-side voltage at zero, so . The rotor accelerates from to .
Step 3: Area available after clearing
Since , the system is stable.
Step 4: Maximum swing angle
Set :
Solving by trial (or numerically): rad.
Answer: Power delivered = 0.821 pu; the system is stable; maximum swing .
For reference, the critical clearing angle for this case is , so clearing at leaves a wide margin.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Critical clearing angle/time, fault at infinite bus · Power System Analysis II, chapter 6
- Rotor angle and swing equation, infinite bus · Power System Analysis II, chapter 6
- Fault cleared at 30°, Pe = 2.1 sin δ · Power System Analysis II, chapter 6
- Mid-line fault, cleared at 60° · Power System Analysis II, chapter 6
- Critical clearing, fault at infinite bus, H = 6 · Power System Analysis II, chapter 6
- Mid-line fault cleared at 60°, E = 1.04 · Power System Analysis II, chapter 6
- Power transfer and pf of motor on infinite bus · Electric Machines II, chapter 2
- Maximum power over 20 + j50 Ω line · Power System Analysis I, chapter 6
- Maximum power over 20 + j30 Ω line · Power System Analysis I, chapter 6
- Power delivered from sending end data, nominal-π · Power System Analysis I, chapter 5