- 2076 Chaitra · 6 marks
Short circuit MVA at bus 2
Short answer
Using Thevenin reactance at bus 2 on 100 MVA base, the short-circuit MVA is 365.9 MVA.
In the network given below, compute the short circuit MVA for a fault at bus 2. [Figure: generator j0.1 - transformer j0.12 - bus 1; line 1-2 j0.08; line 1-3 j0.06; line 2-3 j0.1; Sbase = 100 MVA]
Base: 100 MVA. Pre-fault voltage is taken as 1.0 pu and pre-fault load current is neglected (usual assumption for fault level calculation). Only one source (the generator) feeds the network.
E=1--j0.1--j0.12--bus1
/ \
j0.08 j0.06
/ \
bus2 --j0.1-- bus3
|
F
Thevenin reactance at bus 2
- Source to bus 1: pu.
- Bus 3 has no source, so lines 1-3 and 3-2 are simply in series: pu.
- This path is in parallel with line 1-2 (0.08 pu):
Short-circuit MVA
Answer: short-circuit MVA at bus 2 MVA (fault current 3.659 pu).
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Fault MVA at bus 5 with inductive lines · Power System Analysis II, chapter 3 · asked 2×
- DLG fault at bus 2, fault MVA · Power System Analysis II, chapter 5
- L-L fault current in kA at bus 3 · Power System Analysis II, chapter 5
- L-G fault at bus 1 through Zf · Power System Analysis II, chapter 5
- Generator-reactor system fault MVA · Power System Analysis II, chapter 3
- LLG fault sequence currents at bus 3 · Power System Analysis II, chapter 5
- Per unit values: 100 MVA generator, two motors · Power System Analysis I, chapter 3
- Bus reactor between 100 MVA and 200 MVA generators · Power Plant Equipment, chapter 4
- Per unit circuit of three-generator system, 30 MVA base · Power System Analysis I, chapter 3
- Fault level: four 25 MVA generators, bus reactor · Power Plant Equipment, chapter 4