Short answer

On 100 MVA base, generator reactances are 0.1 pu and 0.04 pu. To limit fault level to 1500 MVA, total equivalent reactance must be 0.0667 pu; solving the parallel paths yields a bus-bar reactor of 0.16 pu.

A 100 MVA generator with 10% reactance and a 200 MVA generator with 8% reactance are connected to a common bus. The fault level on bus 1 is to be restricted to 1500 MVA. If a reactor is added in between these two generators in the bus bar, then on 100 MVA base Calculate the value of reactance added.

The bus-bar is split into two sections joined by a reactor XX: G1 on bus 1 and G2 on bus 2. For a fault on bus 1, G1 feeds directly and G2 feeds through XX. Fault MVA =MVAb/Xeq=\text{MVA}_b/X_{eq}.

Base: 100 MVA.

XG1=0.10 pu,XG2=0.08×100200=0.04 puX_{G1} = 0.10\ \text{pu},\qquad X_{G2} = 0.08\times\frac{100}{200} = 0.04\ \text{pu}
  G1 100MVA,10%        G2 200MVA,8%
       |                     |
  ===[Bus 1]=====[ X ]=====[Bus 2]===
       |
       F (fault on bus 1)

Without reactor: Xeq=0.1∥0.04=0.02857X_{eq} = 0.1\parallel0.04 = 0.02857 pu, fault MVA =100/0.02857=3500= 100/0.02857 = 3500 MVA (too high).

With reactor: required

Xeq=1001500=0.06667 puX_{eq} = \frac{100}{1500} = 0.06667\ \text{pu}

The two paths are in parallel:

1Xeq=1XG1+1XG2+X15=10+10.04+X0.04+X=15=0.2X=0.16 pu\begin{aligned} \frac{1}{X_{eq}} &= \frac{1}{X_{G1}} + \frac{1}{X_{G2}+X} \\ 15 &= 10 + \frac{1}{0.04+X} \\ 0.04 + X &= \frac{1}{5} = 0.2 \\ X &= 0.16\ \text{pu} \end{aligned}

Answer: Bus-bar reactor XX = 0.16 pu (16 %) on 100 MVA base. (If the bus voltage VV kV is known, XΩ=0.16 V2/100X_\Omega = 0.16\,V^2/100; e.g. at 11 kV, 0.194 Ω.)

✓ Answer checked by Claude Opus 5.5 (high effort)