- 2072 Kartik · 8 marks
Star system with three loads, neutral current
Short answer
Line currents: I_R = 9.24 A ∠0°, I_Y = 20.99 A ∠-100°, I_B = 15.40 A ∠110°. Total power = 10.2 kW. Neutral current = 6.2 A (phasor sum of three line currents).
A three phase star connected system with line voltage 400 V is connected to three loads: 25∠0°, 11∠-20° and 15∠10° (also connected in star). Find the line to line current, total power and current in the neutral of the system.
Taking the three loads Z_R = 25∠0° Ω, Z_Y = 11∠−20° Ω, Z_B = 15∠10° Ω as star connected with a neutral wire, in RYB sequence. The loads are unbalanced.
V_ph = 400/√3 = 230.9 V. Take V_R = 230.9∠0°, V_Y = 230.9∠−120°, V_B = 230.9∠+120° V.
Line currents
- I_R = 230.9∠0° / 25∠0° = 9.24 A ∠0°
- I_Y = 230.9∠−120° / 11∠−20° = 20.99 A ∠−100°
- I_B = 230.9∠120° / 15∠10° = 15.40 A ∠+110°
In rectangular form: I_R = 9.24 + j0; I_Y = −3.65 − j20.67; I_B = −5.27 + j14.47 A.
Neutral current
I_N = I_R + I_Y + I_B = (9.24 − 3.65 − 5.27) + j(0 − 20.67 + 14.47) = 0.32 − j6.20 A
|I_N| = 6.2 A (at about −87°)
Total power
P = Σ I²R_load, with R = Z cos θ of each load:
- Phase R: 9.238² × 25 × cos 0° = 2133 W
- Phase Y: 20.995² × 11 × cos(−20°) = 4556 W
- Phase B: 15.396² × 15 × cos 10° = 3502 W
Total P = 10 191 W ≈ 10.2 kW
Answer: line currents 9.24 A, 20.99 A, 15.40 A; total power about 10.19 kW; neutral current about 6.2 A.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Neutral current and power, unbalanced star · Basic Electrical Engineering, chapter 8
- Delta connected coils line current and power · Basic Electrical Engineering, chapter 8
- Star load (8+j6) line, phase current · Basic Electrical Engineering, chapter 8
- Star three impedances four-wire system · Basic Electrical Engineering, chapter 8
- Phase and line voltage in star · Basic Electrical Engineering, chapter 8
- Neutral current and power, 380 V unbalanced load · Basic Electrical Engineering, chapter 8
- Reactance diagram: 20 MVA generator, 15 kV/25 MVA base · Power System Analysis I, chapter 3
- Bresenham: line (25,20) to (15,10) · Computer Graphics, chapter 2
- Single-phase Cu cable for three loads · Industrial Power Distribution and Illumination, chapter 5
- 400 kV quadruple bundle line, 20 m spacing · Power System Analysis I, chapter 4