- 2074 Bhadra · 8 marks
Transformer equivalent circuit referred to primary
Short answer
Secondary parameters are referred to primary by dividing voltage by K, multiplying current by K, and dividing impedances (R, X, Z) by K^2, where K=N2/N1. Equivalent series resistance R01 = R1 + R2/K^2 and reactance X01 = X1 + X2/K^2. Shunt branch remains unchanged.
Draw the equivalent circuit of a transformer with their parameters as it is in primary side and secondary side. How all parameters can be transferred to primary side - explain with mathematical derivation.
The equivalent circuit of a transformer is a circuit of resistances and reactances that behaves exactly like the real transformer, so its performance can be calculated by simple circuit analysis.
Exact equivalent circuit
I1 R1 X1 I2' R2' X2'
o--->-/\/\--mmm--+--------+-->--/\/\--mmm--o
+ | I0 | +
[ R0 ] [ X0 ]
V1 E1 | | V2'
- | | -
o----------------+--------+----------------o
primary side | secondary referred
Parameters:
- : primary winding resistance and leakage reactance.
- : secondary resistance and leakage reactance.
- : core-loss resistance (carries , the working component of ).
- : magnetising reactance (carries ).
In the actual transformer, are on the primary side and and the load are on the secondary side, joined by an ideal transformer of ratio .
Transferring secondary quantities to primary
The rule: the referred quantity must give the same power, losses and VA as the original.
Voltage: since ,
Current: by ampere-turn balance ,
Resistance: copper loss must be unchanged:
Reactance: reactive power must be unchanged:
Load impedance: similarly .
Check with impedance: .
Approximate equivalent circuit referred to primary
Since is only 2-5% of rated current, the shunt branch can be moved to the input terminals. Then the series parts combine:
o---+--------+----[ R01 ]----[ jX01 ]----o
| | +
[ R0 ] [ jX0 ] V2' = V2/K
| | Z_L' = Z_L/K^2
o---+--------+---------------------------o
Similarly, referred to the secondary: , , and are multiplied by .
Rule to remember: going from the low-voltage side to the high-voltage side, impedances are multiplied by the square of the voltage ratio (HV/LV); voltages scale by the ratio, currents by its inverse.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Equivalent circuit and half-load efficiency of 50 kVA transformer · Electrical Machines I, chapter 2
- Equivalent circuit of 5 kVA 200/400 V transformer · Electrical Machines I, chapter 2 · asked 2×
- Equivalent circuit of 10 kVA 250/1000 V transformer · Electrical Machines I, chapter 2 · asked 2×
- Equivalent circuit of 20 kVA 220/2200 V transformer · Electrical Machines I, chapter 2
- OC and SC tests to build transformer equivalent circuit · Electrical Machines I, chapter 2
- Equivalent circuit of 20 kVA 250/2500 V transformer from tests · Electrical Machines I, chapter 2 · asked 3×
- Transformer equivalent circuit, referring parameters · Electrical Machines, chapter 2
- 1000 VA 230/115 V transformer equivalent circuit · Electrical Machines, chapter 2
- 50 kVA transformer: equivalent parameters, copper loss · Electrical Machines, chapter 2
- 20 kVA 2200/220 V tests, equivalent circuit LV side · Electrical Machines, chapter 2