Transformer equivalent circuit, referring parameters
Short answer
The equivalent circuit includes primary R1, X1, secondary R2, X2, and shunt Rc, Xm. To refer secondary to primary, multiply impedances by a^2 (a=N1/N2): R2'=a^2 R2, X2'=a^2 X2. Total referred series impedance is R01=R1+a^2 R2, X01=X1+a^2 X2.
Draw the equivalent circuit of a transformer with their parameters as it is in primary side and secondary side. How all parameters can be transferred to primary side - explain with mathematical derivation.
An equivalent circuit replaces the magnetically coupled windings with an electric network that has the same terminal behaviour. Winding resistance and leakage reactance are put in series, and the core is represented by a shunt branch.
Equivalent circuit (ideal transformer in the centre)
R1 X1 R2 X2
o-/\/\--UUU--+---+----+--/\/\--UUU--o
| | | ideal
V1 Rc Xm ) N1:N2 ( V2 Load
| | |
o------------+---+----+-------------o
- : primary resistance and leakage reactance. : the secondary values.
- : core-loss resistance. : magnetising reactance, with and (where ). Together they form .
- .
Referring all parameters to the primary side
The power in each element must remain the same after referring. Secondary quantities are referred to the primary as follows:
For the secondary impedance, equate the power (and reactive power) before and after referring:
The referred circuit has all the elements on the primary side:
R1 X1 R2' X2'
o-/\/\--UUU--+--/\/\--UUU--+---o
| |
V1 Rc Xm ZL' (= a^2 ZL)
| |
o------------+------------+---o
The total referred values are then
The shunt branch () is often moved to the input terminals (approximate circuit) because is small. With this approximation the circuit is across , followed by in series with .
Referring to the secondary side
Primary quantities are referred to the secondary by dividing by (voltage) and (impedance):
Similarly , , and the primary current becomes .
Rule: an impedance is multiplied by when moved from the secondary to the primary, and divided by when moved from the primary to the secondary, where .
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Transformer equivalent circuit referred to primary · Electrical Machines I, chapter 2
- Equivalent circuit and half-load efficiency of 50 kVA transformer · Electrical Machines I, chapter 2
- 1000 VA 230/115 V transformer equivalent circuit · Electrical Machines, chapter 2
- 50 kVA transformer: equivalent parameters, copper loss · Electrical Machines, chapter 2
- Equivalent circuit of 5 kVA 200/400 V transformer · Electrical Machines I, chapter 2 · asked 2×
- Equivalent circuit of 10 kVA 250/1000 V transformer · Electrical Machines I, chapter 2 · asked 2×
- Equivalent circuit, efficiency and regulation of 5 kVA transformer · Electrical Machines I, chapter 2
- Equivalent circuit of 8 kVA 400/120 V transformer · Electrical Machines I, chapter 2
- Equivalent circuit of 220/440 V transformer · Electrical Machines I, chapter 2
- Determining single phase IM equivalent circuit parameters · Electric Machines II, chapter 3