Regulation of 1.5 MVA generator and zero-regulation pf
Short answer
For 1.4375 MVA load, voltage regulation is 21.15% at 0.8 pf lagging and -13.12% at 0.8 pf leading. Zero regulation occurs at 0.981 leading power factor.
A 3-phase, star connected synchronous generator is rated at 1.5 MVA, 11 kV. The armature effective resistance and synchronous reactance are 1.2 Ω and 25 Ω respectively per phase. Calculate the percentage voltage regulation for a load of 1.4375 MVA at i) 0.8 p.f. lagging and ii) 0.8 p.f. leading. Also find out the p.f. at which regulation is zero.
Given: star, 1.5 MVA, 11 kV, , ; load 1.4375 MVA at 0.8 pf.
(i) 0.8 pf lagging
(ii) 0.8 pf leading
Power factor for zero regulation
For , with and current angle (leading positive):
Answer: (i) 21.15%; (ii) −13.12%; zero regulation at pf = 0.981 leading.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Regulation of delta connected 1600 kVA alternator · Electric Machines II, chapter 1
- Emf, regulation and loading with given load impedance · Electric Machines II, chapter 1
- Synchronous reactance and regulation from test data · Electric Machines II, chapter 1
- Regulation of 10 kVA round-rotor generator · Electric Machines II, chapter 1
- 25 MVA salient pole motor maximum power · Electric Machines II, chapter 2 · asked 3×
- Internal emf, no-load emf and regulation · Electric Machines II, chapter 1
- 5 MVA alternator: regulation and pf for zero regulation · Electrical Machines, chapter 6
- Reactance diagram: 20 MVA generator, 15 kV/25 MVA base · Power System Analysis I, chapter 3
- Reactance diagram: 90 MVA generator (25%), two motors · Power System Analysis I, chapter 3 · asked 2×
- Reactance diagram: 300 MVA, 20 kV generator, two motors · Power System Analysis I, chapter 3