Regulation of 100 kVA alternator from tests
Short answer
DC resistance per phase is 0.5 Ω, effective Ra=0.8335 Ω. From OC and SC tests at same field current: Zs=4.62 Ω, Xs=4.544 Ω. At full load 0.8 pf lagging, generated emf per phase E=829.7 V, voltage regulation=30.64%.
The data obtained on 100 kVA, 1100 V, Y-connected, 3-phase alternators are: DC resistance Test: Voltage between lines 6 V DC, current in lines = 6 A Open Circuit Test: Field Current = 12.5 A DC, line voltage = 420 V AC Short Circuit Test: Field Current = 12.5 A DC, line current = rated current Calculate the voltage regulation of alternator at 0.8 p.f. lagging. Take effective resistance to be 1.667 times of DC resistance.
Regulation is found by the synchronous impedance (EMF) method.
Armature resistance
DC test between two lines (star: two phases in series):
Synchronous impedance (same field current 12.5 A)
Regulation at full load, 0.8 pf lagging
Answer: = 4.62 Ω, = 4.544 Ω, regulation at 0.8 pf lagging = 30.64% (full load assumed).
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Regulation of delta connected 1600 kVA alternator · Electric Machines II, chapter 1
- Synchronous reactance and regulation from test data · Electric Machines II, chapter 1
- Emf and regulation of 1500 kVA 13 kV alternator · Electric Machines II, chapter 1
- Emf and regulation of 1500 kVA alternator · Electric Machines II, chapter 1 · asked 2×
- Power angle and regulation of 10 kVA alternator · Electric Machines II, chapter 1
- Regulation of 10 kVA round-rotor generator · Electric Machines II, chapter 1
- 1600 kVA alternator: emf, regulation, power angle · Electrical Machines, chapter 6
- Equivalent circuit, efficiency and regulation of 5 kVA transformer · Electrical Machines I, chapter 2
- Fault current: two 500 kVA alternators · Power Plant Equipment, chapter 4
- 20 kVA 250/2500 V tests, regulation, efficiency · Electrical Machines, chapter 2