Effect of excitation on synchronous motor
With the help of phasor diagrams, explain the effect of excitation on the power factor of a three phase synchronous motor.
Principle
A synchronous motor runs at constant speed. For a constant load and constant supply voltage , the power input stays constant, so the active component of the armature current stays constant. When the field excitation is changed, the back emf changes, and the current adjusts so that only its reactive component changes. This changes the power factor. (Armature resistance is neglected.)
The phasor relation for a motor is .
Three conditions
- Normal excitation: . The current is minimum, in phase with , and the power factor is unity.
- Under-excitation ( smaller): the current lags the voltage. The motor draws reactive power from the supply like an inductive load: lagging power factor. The current is larger than at unity pf.
- Over-excitation ( larger): the current leads the voltage. The motor supplies reactive power to the supply: leading power factor. The current is again larger.
Motor: V = Ef + jIXs (V is the horizontal reference; Ef lags V by delta)
(a) Under-excited: I lags V, Ef is short
O------------------------> V
`-._ /
`-._ Ef / jIXs
`-._ /
`-._ /
`-._/
(b) Normal: I in phase with V, Ef cos(delta) = V
O------------------------> V
`-._ |
`-._ Ef | jIXs
`-._ |
`-._ |
`-._ |
`-._*
(c) Over-excited: I leads V, Ef is long
O------------------------> V
`-._ \
`-._ Ef \ jIXs
`-._ \
`-._ \
`-._ \
`-._ \
`-._ \
`-._*
In each case is drawn from the tip of to the tip of , at ahead of . Because the power is constant, is constant (the tip of moves along a line perpendicular to ), and is constant (the tip of moves along a line parallel to ).
| Excitation | vs | Current | Power factor |
|---|---|---|---|
| Under | low | Lags | Lagging |
| Normal | Minimum | Unity | |
| Over | high | Leads | Leading |
Application
An over-excited synchronous motor running at no load is a synchronous condenser, used for power factor correction. The V-curve plots armature current against field current for each load; the minimum current of each curve corresponds to unity power factor.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Synchronous motor: pf when input rises to 1500 kW · Electrical Machines, chapter 6
- Single phase motor working; effect of air gap · Electrical Machines, chapter 7
- Scott connection for three-phase to two-phase · Electrical Machines I, chapter 2
- 3.3 kV synchronous motor back emf · Electrical Machines, chapter 6 · asked 2×
- Transformer on load and no load, phasor diagrams · Electrical Machines, chapter 2
- Hunting; loaded operation of synchronous motor · Electrical Machines, chapter 6
- Effect of excitation on synchronous motor · Electrical Machine, chapter 6 · asked 6×
- Synchronous motor features, applications and excitation · Electric Machines II, chapter 2
- Salient pole motor excitation and reluctance power · Electric Machines II, chapter 2
- Excitation emf and maximum power of 1.5 MW motor · Electric Machines II, chapter 2