- 2079 Chaitra · 6 marks
Scott connection for three-phase to two-phase
Short answer
Scott connection uses a main transformer with centre-tapped primary across two lines and a teaser transformer with 0.866 N1 winding from the third line to the tap. Secondary voltages are equal and 90 degrees apart, giving a balanced two-phase supply from three-phase mains.
Explain with the help of connection and phasor diagrams, how Scott connections are used to obtain two-phase supply from three-phase mains.
The Scott (T) connection uses two single-phase transformers to convert a balanced three-phase supply into a balanced two-phase supply (two voltages equal in magnitude and 90° apart), or the reverse. It is used for two-phase loads such as electric furnaces and for traction supply.
Connections
- Main transformer: primary of turns connected across two lines B and C, with a centre tap D.
- Teaser transformer: primary of turns (86.6%), connected between line A and the centre tap D.
- Both secondaries have the same number of turns and feed the two phases separately.
A
|
| Teaser primary
| (0.866 N1 turns)
|
B -------D------- C
N1/2 N1/2
Main primary (N1 turns,
centre tapped at D)
Secondaries (N2 turns each):
Teaser sec -> V_T (phase 1)
Main sec -> V_M (phase 2)
Voltage relations (phasor diagram)
Let the line voltage be .
A
/|\
/ | \
/ | \ VAD = 0.866 VL
/ | \ (perpendicular
/ | \ to BC)
B-----D-----C
VL/2 VL/2
- Voltage across the main primary: .
- D is the midpoint of BC, so is the height of the equilateral triangle:
and is at 90° to .
- Volts per turn on the teaser: , the same as on the main. Therefore the secondary voltages are
They are equal in magnitude and 90° apart — a balanced two-phase supply.
Current relations (balanced two-phase load)
- Teaser primary current , flowing in line A.
- It divides equally at D into the two halves of the main primary, where it combines with the main load current; the resulting line currents and are equal in size to and 120° apart, so the three-phase side sees a balanced load.
Points to note
- If the neutral of the three-phase side is wanted, it is at the point on the teaser one-third of its length from D (i.e. at turns from D).
- The two transformers can be identical units if each has 50% and 86.6% tappings, so they are interchangeable.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Three-phase transformer connections · Electrical Machines I, chapter 2
- Fluxes in three-limb core with two air gaps · Electrical Machines I, chapter 1
- Three-phase connections and series RC phasor · Fundamental of Electrical and Electronics Engineering, chapter 3
- Three phase transformer connections and applications · Electrical Machines, chapter 2
- Methods of three-phase connection · Fundamental of Electrical and Electronics Engineering, chapter 3
- Transformer on load, phasor diagrams · Electrical Machine, chapter 2