Skip to main content

Scott connection for three-phase to two-phase

Short answer

Scott connection uses a main transformer with centre-tapped primary across two lines and a teaser transformer with 0.866 N1 winding from the third line to the tap. Secondary voltages are equal and 90 degrees apart, giving a balanced two-phase supply from three-phase mains.

Explain with the help of connection and phasor diagrams, how Scott connections are used to obtain two-phase supply from three-phase mains.

The Scott (T) connection uses two single-phase transformers to convert a balanced three-phase supply into a balanced two-phase supply (two voltages equal in magnitude and 90° apart), or the reverse. It is used for two-phase loads such as electric furnaces and for traction supply.

Connections

  • Main transformer: primary of N1N_1 turns connected across two lines B and C, with a centre tap D.
  • Teaser transformer: primary of 32N1\frac{\sqrt3}{2}N_1 turns (86.6%), connected between line A and the centre tap D.
  • Both secondaries have the same number of turns N2N_2 and feed the two phases separately.
            A
            |
            |  Teaser primary
            |  (0.866 N1 turns)
            |
   B -------D------- C
     N1/2       N1/2
   Main primary (N1 turns,
   centre tapped at D)

  Secondaries (N2 turns each):
   Teaser sec -> V_T (phase 1)
   Main sec   -> V_M (phase 2)

Voltage relations (phasor diagram)

Let the line voltage be VLV_L.

              A
             /|\
            / | \
           /  |  \   VAD = 0.866 VL
          /   |   \  (perpendicular
         /    |    \   to BC)
        B-----D-----C
          VL/2  VL/2
  • Voltage across the main primary: VBC=VLV_{BC} = V_L.
  • D is the midpoint of BC, so VADV_{AD} is the height of the equilateral triangle:
VAD=VL2−(VL2)2=32VL=0.866 VLV_{AD} = \sqrt{V_L^2 - \left(\frac{V_L}{2}\right)^2} = \frac{\sqrt3}{2}V_L = 0.866\,V_L

and VADV_{AD} is at 90° to VBCV_{BC}.

  • Volts per turn on the teaser: 0.866VL0.866N1=VLN1\frac{0.866V_L}{0.866N_1} = \frac{V_L}{N_1}, the same as on the main. Therefore the secondary voltages are
VM=N2N1VL,VT=N20.866N1(0.866VL)=N2N1VLV_{M} = \frac{N_2}{N_1}V_L, \qquad V_{T} = \frac{N_2}{0.866N_1}(0.866V_L) = \frac{N_2}{N_1}V_L

They are equal in magnitude and 90° apart — a balanced two-phase supply.

Current relations (balanced two-phase load)

  • Teaser primary current IA=23N2N1I2=1.155 N2N1I2I_A = \frac{2}{\sqrt3}\frac{N_2}{N_1}I_2 = 1.155\,\frac{N_2}{N_1} I_2, flowing in line A.
  • It divides equally at D into the two halves of the main primary, where it combines with the main load current; the resulting line currents IBI_B and ICI_C are equal in size to IAI_A and 120° apart, so the three-phase side sees a balanced load.

Points to note

  • If the neutral of the three-phase side is wanted, it is at the point on the teaser one-third of its length from D (i.e. at N123\frac{N_1}{2\sqrt3} turns from D).
  • The two transformers can be identical units if each has 50% and 86.6% tappings, so they are interchangeable.

✓ Answer checked by Claude Opus 5.5 (high effort)

All Electrical Machines I chapter 2 questions →