- 2075 Baisakh · 5+3 marks
Three-phase transformer connections
Short answer
Common connections are star-star (Y-y) for small HV units with tertiary, delta-delta (D-d) for large LV high-current loads, star-delta (Y-d) for step-down at substations, and delta-star (D-y) for distribution. Star gives a neutral; delta suppresses third harmonics. Phase shift is 0° for Y-y and D-d, 30° for Y-d and D-y.
Explain the different three phase transformer connections with neat sketch. Write their application also.
A three-phase transformer (or bank of three single-phase units) can have its primary and secondary windings connected in star (Y) or delta (Δ), giving four common connections. Let = turns ratio per phase () and , = primary line voltage and current. In the sketches, S is one phase winding.
1. Star-Star (Y-y)
Primary (Y) Secondary (y)
A B C a b c
| | | | | |
S S S S S S
\ | / \ | /
\ | / \ | /
N n
- Phase voltage = , so less insulation is needed; a neutral is available on both sides.
- Secondary line voltage = , with no phase shift (0°).
- Problems: third-harmonic voltages in the phase voltages, and neutral shifting with unbalanced loads, unless the primary neutral is earthed or a tertiary delta winding is added.
- Use: small high-voltage transformers, and interconnecting systems where both neutrals are needed (with a tertiary winding).
2. Delta-Delta (D-d)
Primary (D) Secondary (d)
A ----+ a ----+
/ \ / \
S S S S
/ \ / \
B +---S---+ C b +---S---+ c
- Line voltage = phase voltage; winding current = .
- No third-harmonic problem (the third-harmonic current circulates inside the delta), and it handles unbalanced loads well.
- If one unit fails, the remaining two can work in open delta (V-V) at 57.7% of the bank rating.
- No neutral is available. Use: large low-voltage, high-current systems and industrial supply.
3. Star-Delta (Y-d)
Primary (Y) Secondary (d)
A B C a ----+
| | | / \
S S S S S
\ | / / \
\ | / b +---S---+ c
N
- Primary star, secondary delta. Secondary line voltage = , with a 30° phase shift.
- The delta secondary suppresses third harmonics; the primary neutral can be earthed.
- Use: step-down transformers at the receiving end of transmission lines (substations).
4. Delta-Star (D-y)
Primary (D) Secondary (y)
A ----+ a b c
/ \ | | |
S S S S S
/ \ \ | /
B +---S---+ C \ | /
n (neutral brought out)
- Primary delta, secondary star. Secondary line voltage = , with a 30° phase shift.
- The star secondary gives a neutral for a 3-phase, 4-wire supply.
- Use: distribution transformers (e.g. 11 kV/400 V in Nepal) and step-up transformers at the generating station.
Summary
| Connection | Sec. line voltage | Phase shift | Main application |
|---|---|---|---|
| Y-y | 0° | Small HV units, with tertiary | |
| D-d | 0° | Large LV, high-current loads | |
| Y-d | 30° | Step-down at substation | |
| D-y | 30° | Distribution, step-up at plant |
Other connections: open delta (V-V) for emergencies or growing loads, and the Scott (T-T) connection for 3-phase to 2-phase conversion.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Scott connection for three-phase to two-phase · Electrical Machines I, chapter 2
- Currents and efficiency of 132/11 kV transformer at 5 MW · Electrical Machines I, chapter 2 · asked 3×
- Voltage regulation of 2 MVA Δ-Y transformer · Electrical Machines I, chapter 2
- Ideal transformer principle and emf equation · Electrical Machines I, chapter 2 · asked 6×
- Transformer operating principle and emf equation · Electrical Machines I, chapter 2 · asked 6×
- Currents and efficiency of 132/11 kV transformer at 4 MW · Electrical Machines I, chapter 2 · asked 3×
- Three phase transformer connections and applications · Electrical Machines, chapter 2
- Three-phase connections and series RC phasor · Fundamental of Electrical and Electronics Engineering, chapter 3
- Output equation of three phase transformer · Electric Machine Design, chapter 3 · asked 2×
- Design: 125 kVA 6600/400 V three phase transformer · Electric Machine Design, chapter 3 · asked 4×