Output equation of three phase transformer

Short answer

For a three-phase core type transformer, the kVA rating is Q = 3.33 f B_m δ K_w A_w A_i × 10⁻³, with f in Hz, B_m in Wb/m², δ in A/m², K_w window space factor, A_w window area in m² and A_i net core area in m². The equation combines voltage per phase E_t = 4.44f B_m A_i and the window ampere-turn relation AT = K_w A_w δ/4.

Derive an output equation for the three phase core type transformer.

The output equation gives the kVA rating of a three-phase core type transformer in terms of the net core area AiA_i, window area AwA_w, flux density BmB_m and current density δ\delta.

   +-------+-------+-------+
   |       |       |       |
  [L|H] W1 [H|L|H] W2 [H|L]
   |  R    |  Y    |  B    |
   +-------+-------+-------+
  3 limbs, 2 windows; each window holds
  LV + HV of two different phases

Step 1: Voltage per phase

Et=4.44fϕm=4.44fBmAi,Vp≈4.44fBmAiTpE_t = 4.44f\phi_m = 4.44fB_mA_i, \qquad V_p \approx 4.44fB_mA_iT_p

Step 2: Copper in a window

A three-phase core type transformer has three limbs and two windows. Each window holds one coil side from each of two adjacent limbs. Each coil side carries the full cross-section of one primary and one secondary winding:

Copper area in a window=2(apTp+asTs)\text{Copper area in a window} = 2(a_pT_p + a_sT_s)

With ap=Ip/δa_p = I_p/\delta, as=Is/δa_s = I_s/\delta and IpTp=IsTs=ATI_pT_p = I_sT_s = AT:

KwAw=2(ATδ+ATδ)=4ATδ  ⇒  AT=KwAwδ4K_wA_w = 2\left(\frac{AT}{\delta} + \frac{AT}{\delta}\right) = \frac{4AT}{\delta} \;\Rightarrow\; AT = \frac{K_wA_w\delta}{4}

Step 3: Output

Q=3VpIp×10−3=3×4.44fBmAiTpIp×10−3=3×4.44fBmAi×KwAwδ4×10−3Q=3.33 f Bm δ Kw Aw Ai×10−3 kVA\begin{aligned} Q &= 3V_pI_p\times10^{-3} = 3\times4.44fB_mA_iT_pI_p\times10^{-3}\\ &= 3\times4.44fB_mA_i\times\frac{K_wA_w\delta}{4}\times10^{-3}\\ Q &= 3.33\,f\,B_m\,\delta\,K_w\,A_w\,A_i\times10^{-3}\ \text{kVA} \end{aligned}

where QQ is the total three-phase rating in kVA.

Use in design

  • First, Et=KQE_t = K\sqrt{Q} (with K≈0.45K \approx 0.45 for distribution and 0.6–0.7 for power transformers) gives ϕm\phi_m and Ai=ϕm/BmA_i = \phi_m/B_m.
  • Then the output equation gives AwA_w, from which window width and height are found with a chosen Hw/WwH_w/W_w ratio (2 to 4).