Effect of excitation on synchronous motor
Short answer
In a synchronous motor with constant load, varying field excitation changes the back emf and armature current. Under-excitation gives lagging power factor; over-excitation gives leading power factor. Unity pf occurs at minimum armature current. Leading pf operation is obtained by over-exciting the field.
With the help of phasor diagrams, explain the effect of excitation on armature current and power factor of a 3-phase synchronous motor, and explain how it can be operated in leading and lagging pf mode.
In a synchronous motor, the field excitation (field current I_f) controls the back emf E_b. At constant supply voltage V and constant load (constant power input), changing I_f changes the armature current I_a and the power factor, but not the speed.
Basis
Per phase, E_r = V − E_b (phasor difference) and I_a = E_r / Z_s, where Z_s = R_a + jX_s. For constant load, the input power per phase V·I_a·cos φ is constant, so the in-phase component I_a cos φ is constant. Only the quadrature component changes with excitation. R_a is neglected in the diagrams, so E_r = jX_s·I_a and I_a lags E_r by 90°. E_b lags V by the load angle δ. E_r is drawn from the tip of E_b to the tip of V.
Phasor diagrams (V as reference, motor mode)
(a) Under-excited: Eb < V, Ia LAGS V
O-------------------------------------->V
\ ------ //
\ ----- // Er
\ ----- ///
\ Eb ------ //
\ Ia -->/
\
\
v
(b) Normal excitation: Ia IN PHASE with V (unity pf, minimum Ia)
O-------------------------------------->V Ia along V
-------- |
-------- | Er
-------- |
Eb -------- |
--->
(c) Over-excited: Eb > V, Ia LEADS V
^ Ia
/
/
//
/
/
O-------------------------------------->V
----------- \\
--------- \\ Er
----------- \\
Eb --------- \\
----->
In every case Er = V - Eb = jXs·Ia, so Ia is 90° behind Er;
Ia cosφ stays the same for constant load.
| Excitation | Back emf E_b | I_a | Power factor | Machine acts as |
|---|---|---|---|---|
| Under-excited | small | lags V | lagging | inductor (R-L load) |
| Normal excited | medium (I_a minimum) | in phase with V | unity | resistor |
| Over-excited | large | leads V | leading | capacitor (supplies lagging kVAR) |
Explanation
- With reduced I_f, E_b is small (less than V). The resultant emf E_r = V − E_b is large and points up and to the right of the E_b tip, so I_a, which is 90° behind E_r, lags V. The motor draws magnetising (lagging reactive) current from the supply, because part of the main flux must be supplied by the stator. This is the lagging pf mode.
- As I_f is increased, E_b rises, E_r shrinks and I_a falls. At one value of I_f, E_r is at right angles to V, and I_a is minimum and in phase with V: unity pf.
- Further increase of I_f (over-excitation) makes E_r larger again, but it now points up and to the left, so I_a leads V. The motor delivers lagging reactive power to the line, i.e. it acts as a capacitor. This is the leading pf mode.
Operating in leading or lagging mode
- To run at leading pf, raise the d.c. field current above the value for unity pf (over-excite). This is used for power-factor correction; a machine run this way without a mechanical load is called a synchronous condenser.
- To run at lagging pf, reduce the field current below that value (under-excite). This is rarely done, as the stability margin is poorer.
- The plot of I_a against I_f for a constant load is the V-curve. Its minimum point is at unity pf.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Effect of excitation on synchronous motor · Electrical Machines, chapter 6 · asked 5×
- Sync motor back emf at 0.5 pf leading · Electrical Machine, chapter 6
- 1500 kVA alternator: excitation emf, voltage at leading pf · Electrical Machines, chapter 6
- Sync generator terminal voltage, leading pf · Electrical Machine, chapter 6 · asked 2×
- 1200 kVA alternator: voltage at leading pf · Electrical Machines, chapter 6 · asked 2×
- Synchronous motor: pf when input rises to 1500 kW · Electrical Machines, chapter 6
- Synchronous motor drawing lagging and leading current · Electric Machines II, chapter 2 · asked 4×
- Effect of excitation on armature current and pf · Electric Machines II, chapter 2 · asked 3×
- Synchronous motor features and lagging/leading operation · Electric Machines II, chapter 2
- Current, pf, power and efficiency of 3.3 kV motor · Electric Machines II, chapter 2