Low frequency induction furnace with half-full hearth

Short answer

For low-frequency induction furnace at 20V secondary: full hearth 500kW at 0.5pf gives Z=4e-4Ω, R=2e-4Ω, X=3.464e-4Ω. Half-full: R'=4e-4Ω, X unchanged. New Z'=5.2915e-4Ω, I'=37,796A. Power absorbed = I'²R' ≈ 571.4 kW, power factor = R'/Z' = 0.756 lagging.

A low frequency induction furnace operating at 20 volts in secondary circuit takes 500 kW at 0.5 pf when the hearth is full. If the secondary voltage be maintained to 20 volts, estimate the power absorbed and the power factor when the hearth is half-full. Assume the resistance of the secondary circuit to be thereby doubled and the reactance to remain the same.

In a low-frequency (core-type) induction furnace the charge forms the short-circuited secondary, so the secondary current is set by the secondary resistance RR and reactance XX.

Given: V2=20V_2 = 20 V, P=500P = 500 kW at pf 0.5 (hearth full). Half-full: R′=2RR' = 2R, XX unchanged.

Secondary impedance when hearth is full

S=Pcos⁡ϕ=5000.5=1000 kVAI2=SV2=1000×10320=50 000 AZ=V2I2=2050 000=4×10−4 ΩR=Zcos⁡ϕ=2×10−4 ΩX=Zsin⁡ϕ=4×10−4×0.866=3.464×10−4 Ω\begin{aligned} S &= \frac{P}{\cos\phi} = \frac{500}{0.5} = 1000\ \text{kVA} \\ I_2 &= \frac{S}{V_2} = \frac{1000 \times 10^3}{20} = 50\,000\ \text{A} \\ Z &= \frac{V_2}{I_2} = \frac{20}{50\,000} = 4 \times 10^{-4}\ \Omega \\ R &= Z\cos\phi = 2 \times 10^{-4}\ \Omega \\ X &= Z\sin\phi = 4\times10^{-4} \times 0.866 = 3.464 \times 10^{-4}\ \Omega \end{aligned}

Hearth half full

R′=2R=4×10−4 Ω,X=3.464×10−4 ΩZ′=(4)2+(3.464)2×10−4=5.2915×10−4 ΩI2′=205.2915×10−4=37 796 AP′=I2′2R′=37 7962×4×10−4=571.4 kWcos⁡ϕ′=R′Z′=45.2915=0.756 lagging\begin{aligned} R' &= 2R = 4 \times 10^{-4}\ \Omega, \quad X = 3.464 \times 10^{-4}\ \Omega \\ Z' &= \sqrt{(4)^2 + (3.464)^2} \times 10^{-4} = 5.2915 \times 10^{-4}\ \Omega \\ I_2' &= \frac{20}{5.2915 \times 10^{-4}} = 37\,796\ \text{A} \\ P' &= I_2'^2 R' = 37\,796^2 \times 4 \times 10^{-4} = 571.4\ \text{kW} \\ \cos\phi' &= \frac{R'}{Z'} = \frac{4}{5.2915} = 0.756\ \text{lagging} \end{aligned}

Answer: With the hearth half full, power absorbed ≈571.4\approx 571.4 kW at a power factor of 0.7560.756 lagging.