Low frequency induction furnace with half-full hearth
Short answer
For low-frequency induction furnace at 20V secondary: full hearth 500kW at 0.5pf gives Z=4e-4Ω, R=2e-4Ω, X=3.464e-4Ω. Half-full: R'=4e-4Ω, X unchanged. New Z'=5.2915e-4Ω, I'=37,796A. Power absorbed = I'²R' ≈ 571.4 kW, power factor = R'/Z' = 0.756 lagging.
A low frequency induction furnace operating at 20 volts in secondary circuit takes 500 kW at 0.5 pf when the hearth is full. If the secondary voltage be maintained to 20 volts, estimate the power absorbed and the power factor when the hearth is half-full. Assume the resistance of the secondary circuit to be thereby doubled and the reactance to remain the same.
In a low-frequency (core-type) induction furnace the charge forms the short-circuited secondary, so the secondary current is set by the secondary resistance and reactance .
Given: V, kW at pf 0.5 (hearth full). Half-full: , unchanged.
Secondary impedance when hearth is full
Hearth half full
Answer: With the hearth half full, power absorbed kW at a power factor of lagging.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Induction furnace at 10 V, half-full hearth · Utilization of Electrical Energy, chapter 5 · asked 2×
- Arc furnace: kW input, arc voltage, pf, kVA · Utilization of Electrical Energy, chapter 5
- Arc furnace power factor and time to melt steel · Utilization of Electrical Energy, chapter 5
- Line pf of 35 kW induction motor with capacitors · Utilization of Electrical Energy, chapter 6 · asked 3×
- Secondary voltage, regulation, pf for max regulation · Electrical Machines, chapter 2
- Power factor and disadvantages of low pf · Basic Electrical Engineering, chapter 7 · asked 3×
- 500 kVA transformer efficiency full/half load · Electrical Machine, chapter 2
- 500 kVA transformer efficiency, full and half load · Electrical Machines, chapter 2